Siemens 3VA1010-2ED36-0JA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1010-2ED36-0JA0 SENTRON MCCB, 100 A, 52.5 kA

MPN3VA1010-2ED36-0JA0

Siemens SENTRON 3VA1010-2ED36-0JA0, 3-pole molded case circuit breaker, 100 A at 40 °C, 52.5 kA at 240 V, TM210 release, shunt trip.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1010-2ED36-0JA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA10102ED360AA0

Ratings

3VA1010-2ED36-0JA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C98 A
Current at 60 °C96 A
Current at 65 °C94 A
Current at 70 °C91 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 500 V7.5 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.25 W

Protection & Trip Unit

3VA1010-2ED36-0JA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1010-2ED36-0JA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1010-2ED36-0JA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0

Environmental

3VA1010-2ED36-0JA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1010-2ED36-0JA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

What this MCCB carries

The Siemens 3VA1010-2ED36-0JA0 is a 3-pole SENTRON molded case circuit breaker rated for 100 A continuous at 40 °C, with a TM210 thermal-magnetic overcurrent release and an integrated shunt trip (STL) auxiliary release. Breaking capacity hits 52.5 kA at 240 V, tapering to 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 500 V and 690 V — enough for most industrial panel fault-current levels up to the 240 V secondary side of a distribution transformer. Rated insulation voltage is 800 V, and the breaker is designed for line protection — no communication function, no ground-fault monitoring, and no undervoltage release on this variant.

Thermal derating and panel fit

At 40 °C, 45 °C, and 50 °C the breaker holds a full 100 A; derating begins at 55 °C (98 A), dropping to 91 A at 70 °C. That 70 °C operating maximum matches the upper end of the ambient range, so the breaker can sit in a warm enclosure without forced cooling as long as load current stays under the derated curve. Dimensions are 70 mm deep, 76.2 mm wide, and 130 mm tall — a standard 3-pole MCCB footprint that fits most Siemens SENTRON panelboards and third-party enclosures without re-drilling. Maximum power loss is 25 W; account for that heat in the enclosure thermal budget if the breaker is fully loaded in a sealed cabinet.

Frequently asked questions

What does the TM210 release mean on this breaker?

The TM210 is a thermal-magnetic overcurrent release — the thermal element handles overload protection with a fixed time curve, and the magnetic element provides instantaneous short-circuit protection, tuned for line-protection duty.

Does this MCCB include a shunt trip?

Yes, it is fitted with a shunt trip (STL) auxiliary release, allowing remote tripping via a control voltage signal.

MPN
3VA1010-2ED36-0JA0