Specifications

3VA1010-2ED42-0BC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1010-2ED42-0BC0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C96 A
Current at 60 °C94 A
Current at 65 °C92 A
Current at 70 °C90 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 690 V7.5 kA
3VA1010-2ED42-0BC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1010-2ED42-0BC0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1010-2ED42-0BC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts2
3VA1010-2ED42-0BC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1010-2ED42-0BC0 — Mechanical
ParameterValue
Height130 mm
Width101.6 mm
Depth70 mm

Product details

The Siemens SENTRON 3VA1010-2ED42-0BC0 is a 4-pole molded case circuit breaker rated for 100 A continuous current (Iu) with a TM210 thermal-magnetic release — the 210 frame size means the thermal element is fixed at 100 A, no external adjustment. It is a line-protection version, not a motor-protection or ground-fault variant, so it is sized for feeder and distribution circuits where the load is resistive or general-purpose, not for individual motor starting duty. The interrupting ratings climb to 52.5 kA at 240 V AC and 32 kA at 415 V AC, so it handles high-fault-capacity panels in industrial switchboards or building mains.

Above that, it steps down: 96 A at 55 °C, 94 A at 60 °C, 92 A at 65 °C, and 90 A at 70 °C. If the enclosure runs hot (say, next to a drive or transformer), factor the 55 °C column into your load schedule.

Factory-fitted with 2 auxiliary switches (HQ type — high-qualified, meaning higher reliability for signal circuits) and an undervoltage release (UVR).

The 101.6 mm width is a standard 4-pole MCCB footprint — it occupies four 25.4 mm (1-inch) module spaces on a DIN rail or panel-mount base. Front protection is IP40, so it is suitable for enclosed switchboards but not washdown areas. No N-conductor protection (the 4th pole is a switched neutral, not a protected pole).

Frequently asked questions

Where can I buy 3VA1010-2ED42-0BC0 and how do I get a price?

We source this part to order against an RFQ. Availability and current pricing are confirmed at quote time — submit an RFQ and we will respond with a firm price and lead time.

Will 3VA1010-2ED42-0BC0 drop into a panel that was specified around 3VA1010-2ED42-0AE0 without rewiring?

Both are 4-pole 100 A SENTRON MCCBs with the same 130 mm height, 101.6 mm width, and 70 mm depth, so the physical footprint is identical. The difference is the release: the -0AE0 carries a TM240 release (adjustable thermal), while the -0BC0 carries a TM210 (fixed thermal). If the panel wiring and bus bars fit one, they will fit the other — no rewiring needed for the enclosure fit.

What is 3VA1010-2ED42-0BC0's listed depth (70 mm) on this component line?

The depth is 70 mm, which is the dimension from the mounting surface to the front of the breaker body — excludes any protruding handle or aux switch cover.

What is 3VA1010-2ED42-0BC0's listed width (101.6 mm) on this component line?

The width is 101.6 mm, which is the standard 4-pole MCCB module width (four 25.4 mm spaces).

MPN
3VA1010-2ED42-0BC0