Its breaking capacity reaches 52.5 kA at 240 V AC and 32 kA at 415 V AC — figures that govern its ability to safely interrupt fault currents without upstream coordination failure. The 100 A rating holds across 40 °C to 50 °C ambient, then derates to 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C.
The MCCB measures 101.6 mm wide, 130 mm tall, and 70 mm deep — a standard 4-pole MCCB footprint for DIN-rail or panel-mount installation in distribution boards and motor control centers. The 70 mm depth fits typical enclosure depths without crowding gland plates or busbar runs.