Skip to main content
Siemens 3VA1010-2ED42-0CH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1010-2ED42-0CH0 SENTRON MCCB, 100 A, 4-Pole, Line

MPN3VA1010-2ED42-0CH0

Siemens SENTRON 3VA1010-2ED42-0CH0, molded case circuit breaker, 4-pole, 100 A rated continuous current Iu, line protection, TM210 overcurrent release, undervoltage release, IP40 front protection.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1010-2ED42-0CH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA1010-2ED42-0CH0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C96 A
Current at 60 °C94 A
Current at 65 °C92 A
Current at 70 °C90 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 690 V7.5 kA

Protection & Trip Unit

3VA1010-2ED42-0CH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210

Construction & Connection

3VA1010-2ED42-0CH0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1010-2ED42-0CH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts3

Environmental

3VA1010-2ED42-0CH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1010-2ED42-0CH0 — Mechanical
ParameterValue
Height130 mm
Width101.6 mm
Depth70 mm

Product details

What this MCCB is and what it does

The Siemens 3VA1010-2ED42-0CH0 is a SENTRON molded case circuit breaker (MCCB) sized for line protection in distribution panels. It carries a rated continuous current Iu of 100 A and is built as a 4-pole unit, meaning it switches all three phases plus the neutral conductor. The overcurrent release is a TM210 thermal-magnetic type, which provides both overload (thermal) and short-circuit (magnetic) protection without electronic adjustment. Breaking capacity varies with system voltage: 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V. These figures tell you the maximum fault current the breaker can safely interrupt at each voltage level — critical for selectivity studies and SCCR compliance in the panel. The unit includes an undervoltage release (UVR) as the auxiliary release design, plus a built-in auxiliary contact block with 2 auxiliary switches and 1 trip alarm switch (HQ version). A trip indicator is present on the front. The integrated auxiliary trip accessory order code is 3VA9608-0BB24.

Thermal derating and operating range

Rated current holds at 100 A from 40 °C through 50 °C ambient. Above that, derating is gradual: 96 A at 55 °C, 94 A at 60 °C, 92 A at 65 °C, and 90 A at 70 °C. If your panel ambient runs hot — near the upper end of the operating range (−25 °C to 70 °C) — factor in that 10 % reduction at 70 °C to avoid nuisance tripping on a fully loaded circuit. Storage temperature span is −40 °C to 80 °C, which covers most warehouse and shipping conditions without special handling. The front face carries IP40 protection — suitable for dry indoor panel mounting, not for washdown or outdoor exposure.

Panel fit and integration notes

Dimensions are 101.6 mm wide, 130 mm high, and 70 mm deep. The 4-pole width (101.6 mm) matches the standard SENTRON 3VA1 4-pole footprint — a panel originally specified for a 3VA1010-2ED36-0AC0 will accept this unit without rewiring, provided the busbar and lug kit are compatible with the 100 A rating. Rated insulation voltage Ui is 800 V, which covers 690 V systems with margin. No communication function, no phase failure detection, and no ground fault monitoring are built in — this is a straightforward thermal-magnetic line protection breaker, not a power monitoring device. Latching endurance is rated at 15 000 operations. For applications requiring frequent switching (e.g., motor circuits cycled multiple times per shift), consider whether a contactor or motor-protective breaker with higher mechanical endurance is more appropriate.

MPN
3VA1010-2ED42-0CH0