The overcurrent release is a TM210 thermal-magnetic type, which provides both overload (thermal) and short-circuit (magnetic) protection without electronic adjustment. Breaking capacity varies with system voltage: 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V. A trip indicator is present on the front. The integrated auxiliary trip accessory order code is 3VA9608-0BB24.
Above that, derating is gradual: 96 A at 55 °C, 94 A at 60 °C, 92 A at 65 °C, and 90 A at 70 °C.
The 4-pole width (101.6 mm) matches the standard SENTRON 3VA1 4-pole footprint — a panel originally specified for a 3VA1010-2ED36-0AC0 will accept this unit without rewiring, provided the busbar and lug kit are compatible with the 100 A rating. No communication function, no phase failure detection, and no ground fault monitoring are built in — this is a straightforward thermal-magnetic line protection breaker, not a power monitoring device. Latching endurance is rated at 15 000 operations. For applications requiring frequent switching (e.g., motor circuits cycled multiple times per shift), consider whether a contactor or motor-protective breaker with higher mechanical endurance is more appropriate.