Skip to main content
Siemens 3VA1010-2ED42-0DH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1010-2ED42-0DH0 SENTRON MCCB, 100 A, 4-Pole, 52.5

MPN3VA1010-2ED42-0DH0

Siemens SENTRON 3VA1010-2ED42-0DH0, molded case circuit breaker, line protection, 4-pole, 100 A, TM210 release, 52.5 kA at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1010-2ED42-0DH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1010-2ED42-0DH0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C96 A
Current at 60 °C94 A
Current at 65 °C92 A
Current at 70 °C90 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 690 V7.5 kA
3VA1010-2ED42-0DH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1010-2ED42-0DH0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1010-2ED42-0DH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts3
3VA1010-2ED42-0DH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1010-2ED42-0DH0 — Mechanical
ParameterValue
Height130 mm
Width101.6 mm
Depth70 mm

Product details

The Siemens 3VA1010-2ED42-0DH0 is a 4-pole SENTRON molded case circuit breaker rated for 100 A continuous current at 40 °C, with a TM210 thermal-magnetic overcurrent release. Its breaking capacity reaches 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V — figures that tell you where it can safely interrupt a fault without upstream cascading. It's a straight thermal-magnetic device for feeder or main breaker duty in distribution panels, sized for a 100 A bus.

Current derating and temperature

At 55 °C it derates to 96 A, at 60 °C to 94 A, at 65 °C to 92 A, and at 70 °C to 90 A.

Panel fit and auxiliary contacts

The breaker measures 70 mm deep, 101.6 mm wide, and 130 mm high — a standard SENTRON 3VA frame that mounts on a DIN rail or panel plate.

Frequently asked questions

How do I get current pricing and availability for 3VA1010-2ED42-0DH0?

Submit an RFQ through this listing. Availability and pricing are confirmed at quote time through independent distribution channels.

What are the key ratings for 3VA1010-2ED42-0DH0?

Rated continuous current 100 A at 40 °C, 4-pole, breaking capacity 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V. Overcurrent release is TM210.

Will 3VA1010-2ED42-0DH0 drop into a panel specified for 3VA1010-2ED42-0AE0?

Both share the same 3VA frame size — 70 mm depth, 101.6 mm width, 130 mm height — so the physical footprint and mounting are identical. The difference is in the release and accessories; verify the auxiliary contact configuration and undervoltage release match your BOM.

MPN
3VA1010-2ED42-0DH0