Skip to main content
Siemens 3VA1010-2ED42-0JC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1010-2ED42-0JC0 SENTRON MCCB, 100 A, 4-pole, 52.5

MPN3VA1010-2ED42-0JC0

Siemens SENTRON 3VA1010-2ED42-0JC0, molded case circuit breaker, 4-pole, 100 A rated continuous current Iu, TM210 overcurrent release, 52.5 kA at 240 V, 32 kA at 415 V, shunt trip (STL), 2 auxiliary switches HQ, IP40 front.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1010-2ED42-0JC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA1010-2ED42-0JC0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C96 A
Current at 60 °C94 A
Current at 65 °C92 A
Current at 70 °C90 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 690 V7.5 kA

Protection & Trip Unit

3VA1010-2ED42-0JC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210

Construction & Connection

3VA1010-2ED42-0JC0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1010-2ED42-0JC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts2

Environmental

3VA1010-2ED42-0JC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1010-2ED42-0JC0 — Mechanical
ParameterValue
Height130 mm
Width101.6 mm
Depth70 mm

Product details

100 A, 4-pole SENTRON MCCB with TM210 release and shunt trip

The Siemens SENTRON 3VA1010-2ED42-0JC0 is a 4-pole molded case circuit breaker rated for 100 A continuous current at up to 50 °C ambient, with a TM210 thermal-magnetic overcurrent release and an integrated shunt trip (STL) for remote tripping. The 52.5 kA interrupting rating at 240 V gives it headroom for high-fault panelboards; at 415 V it still breaks 32 kA, and at 690 V it clears 7.5 kA — useful for mixed-voltage distribution where a single breaker frame covers multiple secondary feeds.

Thermal derating and ambient limits

The breaker holds its full 100 A rating up to 50 °C. Above that it derates linearly: 96 A at 55 °C, 94 A at 60 °C, 92 A at 65 °C, and 90 A at 70 °C. If the panel ambient runs hot — say inside a non-ventilated enclosure near other heat sources — the 70 °C figure (90 A) is the realistic continuous limit. Operating ambient range is -25 °C to 70 °C; storage range is -40 °C to 80 °C.

Auxiliary and trip configuration

This variant ships with two high-quality auxiliary switches (2 auxiliary switches HQ) for status feedback to a PLC or indication lamp. The shunt trip (STL) allows a remote pushbutton, safety relay, or emergency-stop circuit to open the breaker electrically. The TM210 release is a fixed thermal-magnetic type — no interchangeable trip units, no ground-fault module, no phase-failure detection. The integrated auxiliary trip accessory is order code 3VA9688-0BL32. No undervoltage release, no communication module, no N-conductor protection on this build.

Footprint and panel fit

The breaker measures 70 mm deep, 101.6 mm wide, and 130 mm tall. It mounts on a DIN rail or directly to a backplate via the 3VA mounting base. The 4-pole width (101.6 mm) is standard for a 100 A frame — verify busbar or lug spacing if replacing an older 3-pole unit. The IP40 front protection means it is suitable for enclosed panel mounting; no washdown or outdoor rating on the front face.

Frequently asked questions

Where can I buy 3VA1010-2ED42-0JC0 and how do I get a price?

We source this part through independent distribution channels and quote it to order against an RFQ. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What are the interrupting ratings for 3VA1010-2ED42-0JC0 at different voltages?

The breaker clears 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V.

What is the rated continuous current and how does it derate with temperature?

The rated continuous current Iu is 100 A up to 50 °C. Above that it derates: 96 A at 55 °C, 94 A at 60 °C, 92 A at 65 °C, and 90 A at 70 °C.

What auxiliary and trip options does this MCCB include?

It has a shunt trip (STL) for remote tripping and two high-quality auxiliary switches (2 auxiliary switches HQ) for status feedback. No undervoltage release, no ground-fault module, no communication module.

What are the physical dimensions of 3VA1010-2ED42-0JC0?

The breaker is 70 mm deep, 101.6 mm wide, and 130 mm tall.

MPN
3VA1010-2ED42-0JC0