Skip to main content
Siemens 3VA1010-3ED32-0AC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1010-3ED32-0AC0 SENTRON MCCB, 100A, 3-Pole, TM210

MPN3VA1010-3ED32-0AC0

Siemens SENTRON 3VA series, Molded case circuit breaker, 3VA1010-3ED32-0AC0, 3-pole, 100 A at 40 °C, TM210 thermal-magnetic release, 75.6 kA interrupting at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1010-3ED32-0AC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA10103ED320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1010-3ED32-0AC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C98 A
Current at 60 °C96 A
Current at 65 °C94 A
Current at 70 °C91 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V7.5 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.25 W
3VA1010-3ED32-0AC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1010-3ED32-0AC0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1010-3ED32-0AC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts2
3VA1010-3ED32-0AC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1010-3ED32-0AC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

The Siemens SENTRON 3VA1010-3ED32-0AC0 is a 3-pole molded case circuit breaker rated for line protection, carrying 100 A continuously at 40 °C with no derating up to 50 °C.

At 240 V the breaker interrupts 75.6 kA — enough for high-fault utility feeds. At 415 V it still clears 52.5 kA, dropping to 32 kA at 440 V and 7.5 kA at 500 V and 690 V.

Full 100 A rating holds through 50 °C ambient. Above that it steps down: 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, 91 A at 70 °C. Maximum power dissipation is 25 W — useful for enclosure heat-calc when packing multiple breakers in a row.

Physical fit and auxiliary configuration

It ships with two factory-fitted HQ auxiliary switches — no separate add-on module needed for basic status feedback. Undervoltage release and shunt trip are not built in (no voltage trigger, no undervoltage release); if your circuit requires either, you add them externally or choose a variant that includes them.

Frequently asked questions

How do I get current pricing and availability for 3VA1010-3ED32-0AC0?

Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels.

What is the difference between 3VA1010-3ED32-0AC0 and 3VA1110-5ED36-0AC0?

The 3VA1110-5ED36-0AC0 is a higher-current variant with an electronic overcurrent release (ETU) instead of the TM210 thermal-magnetic release. It also includes communication capability and ground-fault monitoring, which this 3VA1010-3ED32-0AC0 omits. Panel footprint may differ — verify dimensions before substituting.

Will 3VA1010-3ED32-0AC0 drop into a panel specified around 3VA1110-5ED36-0AC0 without rewiring?

Not necessarily. The 3VA1110-5ED36-0AC0 uses an electronic trip unit and may have different accessory slot requirements and wiring for communication and ground-fault connections. Physical dimensions may also differ. Compare the mounting footprint and auxiliary wiring before assuming a drop-in fit.

What compliance documentation does this brand provide for 3VA1010-3ED32-0AC0?

Siemens SENTRON MCCBs typically carry UL, CSA, and IEC certifications. Specific documentation (RoHS, REACH, UL file number, IEC test reports) is available on request with the RFQ.

MPN
3VA1010-3ED32-0AC0