The Siemens SENTRON 3VA1010-3ED32-0DA0 is a 3-pole molded case circuit breaker rated for line protection, carrying a continuous current of 100 A up to 50 °C and derating to 90 A at 70 °C. Its TM210 overcurrent release handles the thermal-magnetic trip curve for feeder and distribution panels. The 75.6 kA breaking capacity at 240 V gives solid fault-clearing headroom on low-voltage switchboards; at 415 V it still breaks 52.5 kA, and at 690 V it holds 7.5 kA — enough for most industrial distribution sections without cascading upstream.
Panel fit and integration
Width 76.2 mm, depth 70 mm, height 130 mm — fits the standard 3-pole MCCB footprint on a DIN rail or panel-mount base. IP40 on the front means it's protected against tools and wires larger than 1 mm, fine for enclosed switchgear but not for washdown zones. The undervoltage release (UVR) is built in, so it drops the breaker on loss of control voltage — common on safety-disconnect circuits. No auxiliary contacts on this variant; if you need status feedback to a PLC, the 3VA9608-0BB25 auxiliary trip block snaps on.
Sourcing and lifecycle
The lifecycle stage is current — this is an active catalog part from the SENTRON 3VA family. No phase-out or last-time-buy notice applies. Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time.