Siemens 3VA1010-3ED32-0JH0 — 100 A SENTRON MCCB for Line Protection
Breaking capacity reaches 75.6 kA at 240 V AC, stepping down to 52.5 kA at 415 V and 32 kA at 440 V (cites:,).
Above 55 °C you derate linearly — 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, 91 A at 70 °C (cites:,). At 690 V the breaking capacity is still 7.5 kA (cites:,). Maximum power loss is 25 W per pole — factor that into enclosure thermal rise calculations (cite:).
The 3VA1010-3ED32-0JH0 measures 130 mm high, 76.2 mm wide, and 70 mm deep — a compact 3-pole footprint that fits standard Siemens SENTRON panel mounting (cites:,). It accepts screw or plug-in terminations; the shunt trip release and auxiliary switch block are pre-installed, so no field assembly of those accessories is needed.