Its breaking capacity steps from 75.6 kA at 240 V down to 7.5 kA at 690 V, so the voltage at the fault point determines whether this breaker clears a high-fault scenario without upstream coordination.
Thermal derating and auxiliary fit
The 100 A rating holds flat from 40 °C to 50 °C, then derates to 91 A at 70 °C.