Specifications

Identification

3VA1010-3ED36-0JA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA10103ED360AA0

Ratings

3VA1010-3ED36-0JA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C98 A
Current at 60 °C96 A
Current at 65 °C94 A
Current at 70 °C91 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V7.5 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.25 W

Protection & Trip Unit

3VA1010-3ED36-0JA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1010-3ED36-0JA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1010-3ED36-0JA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0

Environmental

3VA1010-3ED36-0JA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1010-3ED36-0JA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

What this MCCB delivers

The Siemens SENTRON 3VA1010-3ED36-0JA0 is a 3-pole molded case circuit breaker rated 100 A at 40 °C, with a breaking capacity of 75.6 kA at 240 V — enough headroom for high-fault utility feeds or transformer secondaries where the available short-circuit current is substantial. The TM210 thermal-magnetic release gives fixed thermal and magnetic trip settings, so it's a straight swap for line-protection duty in distribution panels. No communication function, no ground-fault monitoring — this is a bare breaker with a shunt trip (STL) for remote opening.

Integration notes

The 3VA1010-3ED36-0JA0 occupies 70 mm depth, 76.2 mm width, and 130 mm height — standard panel footprint for a 3-pole MCCB in this class. The shunt trip (STL) auxiliary release means you can wire an emergency-stop or undervoltage coil into the breaker without adding an external contactor. Insulation voltage rated 800 V, so it's fine for 480 V and 600 V class systems with margin.

Thermal derating

Rated 100 A continuous at 40 °C, and it holds that rating through 50 °C. Above 55 °C it derates: 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, 91 A at 70 °C. If your panel ambient runs hot, plan for the derated figure.

Frequently asked questions

Who supplies 3VA1010-3ED36-0JA0 and how is it quoted?

This breaker is sourced to order through independent distribution. Submit an RFQ for current availability and pricing — quantities and lead time are confirmed per request.

What is the closest functional second-source to 3VA1010-3ED36-0JA0?

The 3VA1010-2ED32-0JA0 is a direct sibling in the same SENTRON 3VA family. The key difference is the overcurrent release: the -3ED36 carries a TM210, while the -2ED32 uses a different TM release. Both share the same 3-pole frame, 100 A rating, and shunt trip option, so they drop into the same panel footprint without rewiring.

What is the depth of 3VA1010-3ED36-0JA0?

70 mm (2.76 in).

What is the width of 3VA1010-3ED36-0JA0?

76.2 mm (3 in).

Will 3VA1010-3ED36-0JA0 drop into a panel specified around 3VA1010-2ED32-0JA0 without rewiring?

Yes — both breakers share the same 3-pole frame dimensions (70 mm depth, 76.2 mm width, 130 mm height) and the same SENTRON mounting pattern. The shunt trip (STL) wiring is identical. The only difference is the overcurrent release curve (TM210 vs TM on the -2ED32), so verify coordination if selectivity studies were done, but the physical swap is straightforward.