The Siemens SENTRON 3VA1010-3ED42-0AC0 is a 4-pole molded case circuit breaker (MCCB) rated for line protection, carrying a continuous current of 100 A at 40 °C with the TM210 thermal-magnetic release. Rated insulation voltage is 800 V, and the interrupting ratings step from 75.6 kA at 240 V down to 7.5 kA at 690 V — so the SCCR headroom depends on your system voltage. Thermal derating is flat to 50 °C (full 100 A), then drops to 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C — the figure to watch if the breaker lives in a warm enclosure.
Lifecycle and compliance posture
Dimensions are 130 mm high, 101.6 mm wide, and 70 mm deep — standard MCCB footprint for a 4-pole 100 A frame, mounts on a DIN rail or panel-mount adapter.