Skip to main content
Siemens 3VA1010-3ED42-0BA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1010-3ED42-0BA0 SENTRON MCCB, 100 A, 4-Pole, 75.6

MPN3VA1010-3ED42-0BA0

Siemens SENTRON 3VA1010-3ED42-0BA0, molded case circuit breaker, 4-pole, 100 A at 40 °C, TM210 release, 75.6 kA at 240 V, with undervoltage release.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1010-3ED42-0BA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA10103ED420AA0

Ratings

3VA1010-3ED42-0BA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C98 A
Current at 60 °C96 A
Current at 65 °C94 A
Current at 70 °C91 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V7.5 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.27.5 W

Protection & Trip Unit

3VA1010-3ED42-0BA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1010-3ED42-0BA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1010-3ED42-0BA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0

Environmental

3VA1010-3ED42-0BA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1010-3ED42-0BA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.12 in
Width (in)4 in
Depth (in)2.76 in

Product details

What this MCCB carries and where it fits

The Siemens 3VA1010-3ED42-0BA0 is a SENTRON molded case circuit breaker (MCCB) rated for line protection, with a continuous current of 100 A at 40 °C and a 4-pole configuration. Breaking capacity hits 75.6 kA at 240 V, 52.5 kA at 415 V, and 32 kA at 440 V — enough to handle high-fault utility feeds or large transformer secondaries without cascading upstream. The TM210 thermal-magnetic overcurrent release handles the overload and short-circuit protection curve; an integrated undervoltage release (UVR) is built in, so the breaker drops out on loss of control voltage without an external shunt trip module.

Current derating and thermal budget

Rated 100 A from 40 °C through 50 °C ambient, then derates to 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C — useful when the MCCB sits in a crowded panel or near heat sources. Maximum power loss is 27.5 W, which factors into enclosure ventilation calculations for a multi-breaker lineup.

Panel fit and mounting

Width is 101.6 mm (4 in), depth 70 mm (2.76 in), height 130 mm (5.12 in) — standard SENTRON 3VA footprint for a 4-pole frame. Rated insulation voltage is 800 V, so it's suitable for 480/277 V and 600 V panels with headroom to spare.

Frequently asked questions

Does this MCCB include an undervoltage release?

Yes, the design of the auxiliary release is an undervoltage release (UVR), so it trips on loss of control voltage without an external module.

MPN
3VA1010-3ED42-0BA0