Skip to main content
Siemens 3VA1010-3ED42-0DH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1010-3ED42-0DH0 SENTRON MCCB, 100A, 4-Pole, 75.6k

MPN3VA1010-3ED42-0DH0

Siemens SENTRON 3VA1010-3ED42-0DH0, molded case circuit breaker, 4-pole, 100 A at 40 °C, interrupting rating 75.6 kA at 240 V, line protection design with undervoltage release.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1010-3ED42-0DH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA10103ED420AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1010-3ED42-0DH0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C98 A
Current at 60 °C96 A
Current at 65 °C94 A
Current at 70 °C91 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V7.5 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.27.5 W
3VA1010-3ED42-0DH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1010-3ED42-0DH0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1010-3ED42-0DH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts3
3VA1010-3ED42-0DH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1010-3ED42-0DH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.12 in
Width (in)4 in
Depth (in)2.76 in

Product details

The Siemens 3VA1010-3ED42-0DH0 is a SENTRON molded case circuit breaker (MCCB) rated 100 A at 40 °C, with a 4-pole configuration and a maximum interrupting capacity of 75.6 kA at 240 V.

Interrupting Ratings and Thermal Derating

Interrupting capacity varies with voltage: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 7.5 kA at 500 V and 690 V. This means the breaker can safely clear faults up to those levels depending on the system voltage — critical for selectivity studies on a 480 V or 400 V line. Thermal rating holds at 100 A from 40 °C through 50 °C, then derates to 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C.

Physical Fit and Auxiliary Configuration

Dimensions: 70 mm depth, 101.6 mm width, 130 mm height. The 4-pole footprint fits standard panel-mount cutouts for SENTRON 3VA frames.

Frequently asked questions

Where can I buy 3VA1010-3ED42-0DH0 and get a price?

This part is sourced to order against an RFQ through independent distribution. Submit a quote request; availability and current pricing are confirmed at quote time.

What is the interrupting rating of 3VA1010-3ED42-0DH0 at 480 V?

The interrupting rating is 52.5 kA at 415 V and 32 kA at 440 V; at 480 V it falls between those values. For exact coordination, use the 440 V figure as a conservative estimate.

Does 3VA1010-3ED42-0DH0 include an undervoltage release?

Yes, it is equipped with an undervoltage release (UVR) as the auxiliary release, plus two auxiliary switches and one trip alarm switch.

MPN
3VA1010-3ED42-0DH0