Skip to main content
Siemens 3VA1010-3ED42-0KH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1010-3ED42-0KH0 MCCB, 100 A, 4-Pole, 75.6 kA at 2

MPN3VA1010-3ED42-0KH0

Siemens SENTRON 3VA1010-3ED42-0KH0, molded case circuit breaker, 4-pole, 100 A rated continuous current (Iu), TM210 thermal-magnetic release, shunt trip, interrupting rating 75.6 kA at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1010-3ED42-0KH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1010-3ED42-0KH0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C96 A
Current at 60 °C94 A
Current at 65 °C92 A
Current at 70 °C90 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 690 V7.5 kA
3VA1010-3ED42-0KH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1010-3ED42-0KH0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1010-3ED42-0KH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts3
3VA1010-3ED42-0KH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1010-3ED42-0KH0 — Mechanical
ParameterValue
Height130 mm
Width101.6 mm
Depth70 mm

Product details

Line Protection MCCB with TM210 Release

Interrupting capacity is 75.6 kA at 240 V, 52.5 kA at 415 V, and 32 kA at 440 V — enough headroom for most low-voltage switchboards fed by a transformer in the 500–1000 kVA range.

Rated 100 A flat from 40 °C to 50 °C ambient; at 55 °C it derates to 96 A, at 60 °C to 94 A, at 65 °C to 92 A, and at 70 °C to 90 A. Dimensions: 101.6 mm wide, 130 mm high, 70 mm deep. The integrated auxiliary trip is order code 3VA9688-0BL33 — that's the factory-fitted shunt trip coil. If you're replacing an existing breaker, verify the coil voltage matches your control circuit; the base breaker does not include a undervoltage release.

Frequently asked questions

Will 3VA1010-3ED42-0KH0 drop into a panel specified around 3VA1010-2ED32-0JA0?

Yes — same 101.6 mm width, same 4-pole footprint, same TM210 release. The difference is the shunt trip (STL) and the HQ auxiliary/alarm switch on the -3ED42-0KH0; the -2ED32-0JA0 lacks those. No rewiring needed for the power circuit.

MPN
3VA1010-3ED42-0KH0