The TM210 thermal-magnetic overcurrent release handles overloads and short circuits without an external trip unit.
Breaking capacity hits 121 kA at 240 V, 75.6 kA at 415 V, and still holds 11.9 kA at 690 V. That's enough for high-fault panels downstream of a large transformer. The thermal curve is flat from 40 °C to 50 °C at 100 A, then drops to 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C. If the panel runs hot, size the load for the 70 °C number.