Skip to main content
Siemens 3VA1010-4ED32-0HC0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA1010-4ED32-0HC0 MCCB, 100 A, 3-Pole, 121

MPN3VA1010-4ED32-0HC0

Siemens SENTRON 3VA series, molded case circuit breaker (MCCB), 3VA1010-4ED32-0HC0, 3-pole, 100 A at 40 °C, breaking capacity 121 kA at 240 V AC, line protection design with shunt trip release.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1010-4ED32-0HC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA10104ED320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1010-4ED32-0HC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C98 A
Current at 60 °C96 A
Current at 65 °C94 A
Current at 70 °C91 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.25 W
3VA1010-4ED32-0HC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1010-4ED32-0HC0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1010-4ED32-0HC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts2
3VA1010-4ED32-0HC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1010-4ED32-0HC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

Siemens SENTRON 3VA1010-4ED32-0HC0 — 100 A MCCB with Shunt Trip

Its interrupting capacity reaches 121 kA at 240 V AC, stepping down to 75.6 kA at 415 V and 52.5 kA at 440 V — figures that cover most commercial and light-industrial fault-current scenarios without needing a current-limiting upstream device. The basic switch platform is order code 3VA10104ED320AA0, meaning the breaker core itself is a standard 3VA1010 frame; the -4ED32-0HC0 suffix specifies the trip unit, accessories, and terminal configuration.

Above 500 V the breaker holds 11.9 kA, which constrains its use on 690 V systems to locations with low prospective fault current. Thermal current rating holds flat at 100 A from 40 °C through 50 °C, then derates gradually: 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C. In a sealed, uncooled enclosure the panel designer should apply the 70 °C column (91 A) as the effective continuous rating. Maximum power dissipation is 25 W per pole — relevant for heat buildup in compact cabinets.

Mounts via screw-clamp to a backplate or DIN rail adapter.

Frequently asked questions

Will 3VA1010-4ED32-0HC0 drop into a panel specified around 3VA1110-5ED36-0AC0?

No — the 3VA1110-5ED36-0AC0 uses a larger frame (3VA1110) with different mounting hole spacing and busbar pitch. The 3VA1010 frame is physically smaller and will not align with the same cutout or bus connections without panel modification.

MPN
3VA1010-4ED32-0HC0