At 240 V it interrupts 121 kA; at 690 V the rating drops to 11.9 kA — match the SCCR of your panel to the voltage at the fault point.
Fit and integration
Three-pole construction, 76.2 mm wide, 130 mm tall, 70 mm deep — standard MCCB footprint for a 100 A frame. The 70 mm depth leaves clearance inside a 200 mm deep enclosure. No undervoltage release or ground-fault module on this variant.