Siemens 3VA1010-4ED32-0JC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1010-4ED32-0JC0 SENTRON MCCB, 100A, 121kA at 240V

MPN3VA1010-4ED32-0JC0

Siemens SENTRON 3VA1010-4ED32-0JC0, 3-pole molded case circuit breaker, 100 A rated at 40 °C, 121 kA breaking capacity at 240 V AC, line protection design with shunt trip and auxiliary switches.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1010-4ED32-0JC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA10104ED320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA1010-4ED32-0JC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C98 A
Current at 60 °C96 A
Current at 65 °C94 A
Current at 70 °C91 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.25 W

Protection & Trip Unit

3VA1010-4ED32-0JC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1010-4ED32-0JC0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1010-4ED32-0JC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts2

Environmental

3VA1010-4ED32-0JC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1010-4ED32-0JC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

Siemens 3VA1010-4ED32-0JC0 — 100 A SENTRON MCCB, Line Protection with Shunt Trip

The Siemens 3VA1010-4ED32-0JC0 is a 3-pole SENTRON molded case circuit breaker (MCCB) rated for line protection, carrying a continuous current of 100 A at 40 °C ambient. Its interrupting capacity at 240 V AC is 121 kA, which provides substantial fault-current headroom for downstream coordination in distribution panels. The breaker is fitted with a shunt trip release (STL) and two HQ auxiliary switches, enabling remote tripping and status feedback without an additional enclosure.

Breaking Capacity and Coordination

Per the specification, the interrupting capacity is rated at 121 kA at 240 V AC, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at both 500 V and 690 V. For a panel designer performing selectivity analysis, the 121 kA figure at 240 V means this MCCB can safely clear a bolted fault at the main bus without upstream device intervention, provided the available fault current at the line side does not exceed that value. The rated insulation voltage is 800 V, which covers 480/277 V and 600 V nominal systems with margin.

Thermal Derating and Power Loss

The breaker carries 100 A continuously from 40 °C through 50 °C ambient. Derating begins at 55 °C (98 A), stepping down to 91 A at 70 °C. Maximum power loss is 25 W, which should be factored into enclosure thermal calculations, particularly in densely packed panels. Operating temperature range is -25 °C to +70 °C; storage range is -40 °C to +80 °C.

Physical Dimensions and Panel Fit

The 3VA1010-4ED32-0JC0 occupies a 76.2 mm width (3 in), 130 mm height (5.12 in), and 70 mm depth (2.76 in). These dimensions match the standard SENTRON 3VA1 frame footprint, so a panel originally laid out for a 3VA1110-series MCCB will accept this unit without bus-bar or mounting-plate modifications. The 3-pole construction fits directly onto the DIN rail or mounting plate per the manufacturer's installation instructions.

Frequently asked questions

What is the breaking capacity of 3VA1010-4ED32-0JC0 at 240 V?

The interrupting capacity is 121 kA at 240 V AC. At 415 V it is 75.6 kA, at 440 V it is 52.5 kA, and at 500 V and 690 V it is 11.9 kA.

Will 3VA1010-4ED32-0JC0 drop into a panel specified around 3VA1110-5EE32-0LC0 without rewiring?

Yes. Both units share the same SENTRON 3VA1 frame footprint (76.2 mm width, 130 mm height, 70 mm depth) and 3-pole construction, so the physical mounting and bus-bar positions are identical. No rewiring of the panel layout is required for the swap.

Where can I buy 3VA1010-4ED32-0JC0?

This MCCB is sourced and quoted to order against an RFQ through independent industrial-automation distribution. Availability and current pricing are confirmed at the time of quotation.

MPN