Siemens 3VA1010-4ED32-0JC0 — 100 A SENTRON MCCB, Line Protection with Shunt Trip
Per the specification, the interrupting capacity is rated at 121 kA at 240 V AC, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at both 500 V and 690 V.
Derating begins at 55 °C (98 A), stepping down to 91 A at 70 °C. Maximum power loss is 25 W, which should be factored into enclosure thermal calculations, particularly in densely packed panels.
Physical Dimensions and Panel Fit
The 3VA1010-4ED32-0JC0 occupies a 76.2 mm width (3 in), 130 mm height (5.12 in), and 70 mm depth (2.76 in). These dimensions match the standard SENTRON 3VA1 frame footprint, so a panel originally laid out for a 3VA1110-series MCCB will accept this unit without bus-bar or mounting-plate modifications. The 3-pole construction fits directly onto the DIN rail or mounting plate per the manufacturer's installation instructions.