Siemens 3VA1010-4ED36-0AC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1010-4ED36-0AC0 Circuit Breaker, 100A, 36kA @ 415

MPN3VA1010-4ED36-0AC0

Siemens 3VA1 IEC frame 100 circuit breaker, breaking capacity class S, 3-pole, 100A fixed thermal-magnetic overload (TM210), 36kA interrupting capacity @ 415V, clamp terminals, 2 auxiliary switches HQ.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Product details

What the ratings mean for your panel

The Siemens 3VA1010-4ED36-0AC0 is a 3-pole IEC frame 100 molded-case circuit breaker with a 100 A fixed thermal-magnetic overload (TM210) and a short-circuit release set at 10× In (1000 A). The breaking capacity class S delivers 36 kA at 415 V AC — that is the maximum fault current it can safely interrupt without welding contacts or rupturing the case. For a 415 V distribution board, this SCCR covers most industrial transformer-fed busways; if your available fault current exceeds 36 kA, step up to the H (high) or L (very high) breaking capacity variant in the same 3VA1 frame.

Integration notes for the panel builder

Clamp terminals accept copper or aluminium conductors without lug preparation — strip length follows the terminal marking on the breaker body. The two factory-fitted auxiliary switches (HQ designation) provide NO/NC status feedback for PLC or remote indication; they share the same switching capacity as the main contacts and are wired via the screw terminals on the breaker side. Mounts on standard DIN rail or panel-mount via the optional rear-mounting bracket. The 3-pole footprint occupies three 27 mm module widths on the rail.

Frequently asked questions

Where can I buy 3VA1010-4ED36-0AC0 and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing — no stock count or price figure is published here.

What is the breaking capacity of this breaker?

The breaking capacity class S provides Icu = 36 kA at 415 V AC, which is the maximum prospective fault current the breaker can safely interrupt at that voltage.

What does the TM210 designation mean?

TM210 indicates a fixed thermal-magnetic overload release with Ir = 100 A (the continuous current rating) and a short-circuit pickup set at 10 × In (1000 A). The thermal element provides inverse-time overload protection; the magnetic element provides instantaneous short-circuit protection.

MPN