Skip to main content
Siemens 3VA1010-4ED36-0BC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1010-4ED36-0BC0 SENTRON MCCB, 100 A, 3-Pole, Line

MPN3VA1010-4ED36-0BC0

Siemens SENTRON 3VA1010-4ED36-0BC0, molded case circuit breaker, 3-pole, 100 A, line protection, TM210 release, 70 mm depth, 76.2 mm width, 130 mm height.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1010-4ED36-0BC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA1010-4ED36-0BC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C96 A
Current at 60 °C94 A
Current at 65 °C92 A
Current at 70 °C90 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 690 V11.9 kA

Protection & Trip Unit

3VA1010-4ED36-0BC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210

Construction & Connection

3VA1010-4ED36-0BC0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1010-4ED36-0BC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts2

Environmental

3VA1010-4ED36-0BC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1010-4ED36-0BC0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

MCCB for feeder and branch circuit protection

The Siemens SENTRON 3VA1010-4ED36-0BC0 is a 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous current at 40 °C, with a TM210 thermal-magnetic release for line protection in distribution panels and motor control centers. Its interrupting capacity hits 121 kA at 240 V AC and 75.6 kA at 415 V AC, which means it can handle high-fault scenarios at common industrial voltages without cascading failure upstream. The 70 mm depth and 76.2 mm width fit standard SENTRON panel cutouts and busbar spacings, making it a direct swap into existing Siemens MCCB lineups.

Breaking capacity and thermal derating

At 440 V the breaker still clears 52.5 kA; at 690 V it drops to 11.9 kA — the SCCR headroom shrinks as system voltage rises, so coordination studies need the specific voltage point. Thermal derating is minimal through 50 °C (still 100 A), then steps down to 96 A at 55 °C, 94 A at 60 °C, 92 A at 65 °C, and 90 A at 70 °C — usable in warm enclosures if you account for the drop. Rated insulation voltage Ui is 800 V, so the breaker is rated for 690 V systems with margin on the insulation path.

Panel integration and auxiliary options

The breaker ships with 2 auxiliary switches (HQ type) installed — part number 3VA9608-0BB11 — for remote status feedback to a PLC or annunciator. An undervoltage release (UVR) is integrated, so the breaker can be tripped remotely on loss of control voltage — typical for emergency-stop circuits or undervoltage protection schemes. Front protection is IP40, meaning tools and fingers stay out of the live terminals in a closed panel; no washdown rating, so keep it in a dry enclosure.

Frequently asked questions

Will 3VA1010-4ED36-0BC0 drop into a panel designed for 3VA1010-2ED36-0AC0?

Both are 3-pole 100 A SENTRON MCCBs with the same 70 mm depth and 76.2 mm width, so the physical footprint and busbar spacing are identical — no rewiring needed for the mount.

MPN
3VA1010-4ED36-0BC0