Skip to main content
Siemens 3VA1010-4ED36-0CH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1010-4ED36-0CH0 MCCB, 100 A, 121 kA at 240 V

MPN3VA1010-4ED36-0CH0

Siemens SENTRON 3VA1010-4ED36-0CH0, 3-pole molded case circuit breaker, 100 A rated continuous current, TM210 thermal-magnetic release, 121 kA breaking capacity at 240 V AC, undervoltage release, IP40 front protection.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1010-4ED36-0CH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA1010-4ED36-0CH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C96 A
Current at 60 °C94 A
Current at 65 °C92 A
Current at 70 °C90 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 690 V11.9 kA

Protection & Trip Unit

3VA1010-4ED36-0CH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210

Construction & Connection

3VA1010-4ED36-0CH0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1010-4ED36-0CH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts3

Environmental

3VA1010-4ED36-0CH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1010-4ED36-0CH0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

Integrator note — 3VA1010-4ED36-0CH0

The Siemens SENTRON 3VA1010-4ED36-0CH0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection, with a continuous current Iu of 100 A and a TM210 thermal-magnetic release. Breaking capacity hits 121 kA at 240 V, 75.6 kA at 415 V, and 52.5 kA at 440 V — the 415 V figure is the one that matters for most European 400 V distribution panels. At 690 V it drops to 11.9 kA, so verify the fault level if this lands on a 690 V bus. Current rating holds flat at 100 A up to 50 °C ambient; above that it derates to 96 A at 55 °C, 94 A at 60 °C, 92 A at 65 °C, and 90 A at 70 °C. If the panel runs hot — say a crowded enclosure near a furnace line — plan the load at the derated figure, not the nameplate 100 A. Front protection is IP40 — fine for a clean panel interior, not for washdown zones. Operating range spans -25 °C to 70 °C, storage from -40 °C to 80 °C. Built-in undervoltage release (UVR) is standard on this variant. Auxiliary contact block carries 2 auxiliary switches plus 1 trip alarm switch (HQ version). The integrated auxiliary trip order code is 3VA9608-0BB24.

Panel fit — dimensions and mounting

Footprint is 76.2 mm wide, 130 mm tall, 70 mm deep. Standard 3-pole MCCB width — fits a 3-module DIN-rail slot or screw-mount backplate.

Frequently asked questions

How does the 3VA1010-4ED36-0CH0 differ from the 3VA1010-2ED32-0JA0?

The 3VA1010-4ED36-0CH0 includes an undervoltage release (UVR) and a TM210 thermal-magnetic release, while the 3VA1010-2ED32-0JA0 is a different release variant without UVR. Both are 3-pole 100 A MCCBs in the same SENTRON 3VA frame — the 4ED36-0CH0 drops into the same panel footprint and busbar arrangement as the 2ED32-0JA0, but the UVR wiring must be added if the original design didn't call for it.

What auxiliary contacts does this MCCB come with?

It ships with 2 auxiliary switches plus 1 trip alarm switch (HQ configuration). The integrated auxiliary trip order code is 3VA9608-0BB24.

MPN
3VA1010-4ED36-0CH0