The interrupting ratings climb to 121 kA at 240 V and 75.6 kA at 415 V, so it can clear high-fault currents without upstream coordination issues.
The 100 A rating holds from 40 °C through 50 °C, then derates to 96 A at 55 °C, 94 A at 60 °C, 92 A at 65 °C, and 90 A at 70 °C.
Front protection is IP40, so it's suited for dry indoor panels. The TM210 release is fixed — no interchangeable trip units — so the 100 A rating is locked in at order time.