Skip to main content
Siemens 3VA1010-4ED42-0AD0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1010-4ED42-0AD0 SENTRON MCCB, 100 A, 4-Pole, TM21

MPN3VA1010-4ED42-0AD0

Siemens SENTRON 3VA1010-4ED42-0AD0, molded case circuit breaker, 4-pole, 100 A at 40 °C, TM210 overcurrent release, 121 kA interrupting at 240 V, line protection design.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1010-4ED42-0AD0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA10104ED420AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1010-4ED42-0AD0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C98 A
Current at 60 °C96 A
Current at 65 °C94 A
Current at 70 °C91 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.25 W
3VA1010-4ED42-0AD0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1010-4ED42-0AD0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1010-4ED42-0AD0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts3
3VA1010-4ED42-0AD0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1010-4ED42-0AD0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.12 in
Width (in)4 in
Depth (in)2.76 in

Product details

It ships as a 4-pole unit with the basic switch 3VA10104ED420AA0 and three HQ auxiliary switches fitted — no separate accessory order needed for the aux contacts. The interrupting capacity reaches 121 kA at 240 V and 75.6 kA at 415 V, with a rated insulation voltage of 800 V. The kit is complete: no holes in the box for the auxiliary switches.

The 3VA1010-4ED42-0AD0 delivers 121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at both 500 V and 690 V. That spread covers most industrial line-to-line voltages in North America and Europe.

Above that, derate to 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C. Maximum power loss is 25 W.

Width 101.6 mm (4 in), height 130 mm (5.12 in), depth 70 mm (2.76 in). Four-pole footprint matches standard SENTRON 3VA mounting slots. Ground-fault monitoring version is without.

Frequently asked questions

Who supplies 3VA1010-4ED42-0AD0 and how is it quoted for volume purchases?

This part is sourced to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time for any volume.

What is the interrupting capacity of this MCCB at 240 V?

121 kA at 240 V. At 415 V it is 75.6 kA, at 440 V it is 52.5 kA, and at 500 V and 690 V it is 11.9 kA.

What overcurrent release does the 3VA1010-4ED42-0AD0 use?

It uses a TM210 thermal-magnetic overcurrent release — fixed, non-electronic, no programming required.

Does this breaker ship with auxiliary switches?

Yes, it includes three HQ auxiliary switches fitted on the basic switch 3VA10104ED420AA0. No separate accessory order needed.

MPN
3VA1010-4ED42-0AD0