Skip to main content
Siemens 3VA1010-4ED42-0HA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1010-4ED42-0HA0 SENTRON MCCB, 100 A, 121 kA at 24

MPN3VA1010-4ED42-0HA0

Siemens SENTRON, Molded case circuit breaker, 3VA1010-4ED42-0HA0, 100 A rated continuous current, 121 kA at 240 V, 4-pole, line protection, TM210 overcurrent release, shunt trip.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1010-4ED42-0HA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1010-4ED42-0HA0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C96 A
Current at 60 °C94 A
Current at 65 °C92 A
Current at 70 °C90 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 690 V11.9 kA
3VA1010-4ED42-0HA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1010-4ED42-0HA0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1010-4ED42-0HA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA1010-4ED42-0HA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1010-4ED42-0HA0 — Mechanical
ParameterValue
Height130 mm
Width101.6 mm
Depth70 mm

Product details

The interrupting rating drops to 75.6 kA at 415 V and 52.5 kA at 440 V, so verify the available fault current at your system voltage before committing the BOM line. At 690 V the rating is 11.9 kA, which limits this variant to lower-fault installations at that voltage. The overcurrent release is a TM210 — thermal-magnetic, fixed-trip, non-interchangeable. That means the 100 A continuous rating is built in; there is no plug-in rating plug to swap for a different amp frame.

Above that the thermal curve begins to bite: 96 A at 55 °C, 94 A at 60 °C, 92 A at 65 °C, and 90 A at 70 °C. Dimensions are 101.6 mm wide × 130 mm high × 70 mm deep. Front protection is IP40.

Frequently asked questions

Does 3VA1010-4ED42-0HA0 include a shunt trip?

Yes. The breaker is designed with a shunt trip (STL) for remote opening. The integrated auxiliary trip order code is 3VA9688-0BL30.

MPN
3VA1010-4ED42-0HA0