Skip to main content
Siemens 3VA1010-4ED42-0JA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1010-4ED42-0JA0 SENTRON MCCB, 100A, 4-Pole, 121kA

MPN3VA1010-4ED42-0JA0

Siemens SENTRON 3VA1010-4ED42-0JA0, molded case circuit breaker, 4-pole, 100 A rated continuous current, TM210 thermal-magnetic release, shunt trip, line protection, breaking capacity 121 kA at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1010-4ED42-0JA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1010-4ED42-0JA0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C96 A
Current at 60 °C94 A
Current at 65 °C92 A
Current at 70 °C90 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 690 V11.9 kA
3VA1010-4ED42-0JA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1010-4ED42-0JA0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1010-4ED42-0JA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA1010-4ED42-0JA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1010-4ED42-0JA0 — Mechanical
ParameterValue
Height130 mm
Width101.6 mm
Depth70 mm

Product details

MCCB for 100 A feeder and branch protection

Its TM210 thermal-magnetic release provides fixed overload and short-circuit protection without the need for external relays — a straightforward fit for 100 A feeder circuits, busway taps, or large motor branch circuits where adjustable electronic trip is not required. Breaking capacity is 121 kA at 240 V AC, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at 690 V — high enough for most low-voltage distribution systems with high fault current potential.

The 100 A rating holds flat from 40 °C to 50 °C, then derates to 96 A at 55 °C, 94 A at 60 °C, 92 A at 65 °C, and 90 A at 70 °C.

Integrated shunt trip and auxiliary options

Frequently asked questions

Does 3VA1010-4ED42-0JA0 include a shunt trip?

Yes, it ships with a factory-fitted shunt trip release (STL). The integrated auxiliary trip order code is 3VA9688-0BL32.

Will 3VA1010-4ED42-0JA0 drop into a panel specified for 3VA1110-5EE32-0JA0?

Both are 4-pole SENTRON 3VA1 frame breakers with the same 101.6 mm width, so the panel cutout and mounting pattern are identical. The difference is in the release type and rating — the 3VA1110-5EE32-0JA0 carries an electronic trip, while this unit has a fixed TM210 thermal-magnetic release. Mechanically interchangeable, but verify the protection curve and rating match your application.

MPN