Skip to main content
Siemens 3VA1020-2ED36-0AH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1020-2ED36-0AH0 3-Pole MCCB, 20 A, TM210, 52.5 kA

MPN3VA1020-2ED36-0AH0

Siemens SENTRON 3VA1020-2ED36-0AH0, molded case circuit breaker, 3-pole, 20 A rated continuous current, TM210 thermal-magnetic release, 52.5 kA interrupting at 240 V, IP40 front.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1020-2ED36-0AH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1020-2ED36-0AH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C20 A
Current at 45 °C20 A
Current at 50 °C20 A
Current at 55 °C19.2 A
Current at 60 °C18.8 A
Current at 65 °C18.4 A
Current at 70 °C18 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 690 V7.5 kA
3VA1020-2ED36-0AH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1020-2ED36-0AH0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1020-2ED36-0AH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts3
3VA1020-2ED36-0AH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1020-2ED36-0AH0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

Above that, it derates gradually: 19.2 A at 55 °C, 18.8 A at 60 °C, 18.4 A at 65 °C, and 18 A at 70 °C. Interrupting capacity is 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V. For a 20 A frame, those numbers give plenty of SCCR headroom for most distribution panels — you're not bumping up against the breaker's limit on a typical 415 V line.

The 3VA1020-2ED36-0AH0 measures 130 mm high, 76.2 mm wide, and 70 mm deep. That gives you a dedicated alarm contact for remote fault indication — handy for a PLC input or a panel lamp.

Frequently asked questions

Where can I buy 3VA1020-2ED36-0AH0 and get a price?

This part is sourced and quoted to order through independent distribution. Submit an RFQ for current availability and pricing — no stock count or lead time is published here.

What is the interrupting capacity of this breaker at 415 V?

At 415 V the interrupting capacity is 32 kA. It also carries 52.5 kA at 240 V, 13.6 kA at 440 V, and 7.5 kA at 690 V.

Will 3VA1020-2ED36-0AH0 drop into a panel specified around 3VA1010-2ED42-0AE0?

The 3VA1020-2ED36-0AH0 shares the same 3-pole SENTRON frame dimensions (130 mm high, 76.2 mm wide, 70 mm deep) as the 3VA1010-2ED42-0AE0, so it will physically fit without rewiring the bus bars. The difference is the rating: this one is 20 A fixed TM210 versus the other variant's higher amp rating and different release.

MPN
3VA1020-2ED36-0AH0