Skip to main content
Siemens 3VA1020-2ED36-0JA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1020-2ED36-0JA0 SENTRON MCCB, 20 A, 3-pole, 52.5

MPN3VA1020-2ED36-0JA0

Siemens SENTRON 3VA1020-2ED36-0JA0, molded case circuit breaker, 3-pole, 20 A (40 °C), TM210 thermal-magnetic release, shunt trip (STL), breaking capacity 52.5 kA at 240 V AC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1020-2ED36-0JA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA10202ED360AA0
3VA1020-2ED36-0JA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C20 A
Current at 45 °C20 A
Current at 50 °C20 A
Current at 55 °C20 A
Current at 60 °C19 A
Current at 65 °C19 A
Current at 70 °C19 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 500 V7.5 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.12 W
3VA1020-2ED36-0JA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1020-2ED36-0JA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1020-2ED36-0JA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA1020-2ED36-0JA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1020-2ED36-0JA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

Siemens 3VA1020-2ED36-0JA0 — 20 A SENTRON MCCB with shunt trip

The Siemens 3VA1020-2ED36-0JA0 is a 3-pole SENTRON molded case circuit breaker (MCCB) rated 20 A at 40 °C, fitted with a TM210 thermal-magnetic overcurrent release and a factory-integrated shunt trip (STL) for remote opening. Breaking capacity reaches 52.5 kA at 240 V AC, 32 kA at 415 V, and 13.6 kA at 440 V — enough headroom for most secondary distribution boards fed by a transformer of moderate impedance. At 690 V it still interrupts 7.5 kA. That means the 20 A frame is the breaker's identity; if the load grows past 20 A, the whole MCCB gets swapped, not just a trip unit.

Selectivity and coordination

With a 52.5 kA interrupting rating at 240 V and a 20 A continuous frame, this MCCB coordinates well downstream of a larger SENTRON 3VA molded-case or an 3WL air breaker. The TM210's fixed thermal curve means no field-adjustable long-time pickup — selectivity with upstream feeders relies on the manufacturer's published let-through curves, not a dial. The shunt trip (STL) allows a remote trip signal from a safety relay, PLC, or E-stop button — useful for emergency-off circuits or undervoltage protection schemes where a separate undervoltage release is not fitted.

Mounts via rear screw terminals or optional DIN-rail adapter.

Frequently asked questions

What does the TM210 release designation mean?

TM210 refers to a fixed thermal-magnetic overcurrent release rated 20 A — the 'TM' indicates thermal-magnetic (no electronic adjustment), and '210' encodes the 20 A rating. It is not field-interchangeable.

Will 3VA1020-2ED36-0JA0 drop into a panel specified around 3VA1110-5ED36-0AC0 without rewiring?

No — the 3VA1110-5ED36-0AC0 is a higher-frame breaker with different dimensions and a higher continuous rating. The 3VA1020-2ED36-0JA0 uses the smaller 3VA1 frame (76.2 mm wide vs the 3VA11's wider footprint). Panel cutouts and busbar spacing differ; a direct swap is not possible without mechanical modification.

MPN
3VA1020-2ED36-0JA0