Skip to main content
Siemens 3VA1020-3ED36-0HH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1020-3ED36-0HH0 SENTRON MCCB, 20 A, 3-Pole, 75.6

MPN3VA1020-3ED36-0HH0

Siemens SENTRON 3VA1020-3ED36-0HH0, molded case circuit breaker, 3-pole, 20 A, TM210 thermal-magnetic release, line protection, 75.6 kA at 240 V, IP40 front.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1020-3ED36-0HH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA1020-3ED36-0HH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C20 A
Current at 45 °C20 A
Current at 50 °C20 A
Current at 55 °C19.2 A
Current at 60 °C18.8 A
Current at 65 °C18.4 A
Current at 70 °C18 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 690 V7.5 kA

Protection & Trip Unit

3VA1020-3ED36-0HH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210

Construction & Connection

3VA1020-3ED36-0HH0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1020-3ED36-0HH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts3

Environmental

3VA1020-3ED36-0HH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1020-3ED36-0HH0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

Siemens 3VA1020-3ED36-0HH0 — 20 A SENTRON MCCB for Line Protection

The Siemens 3VA1020-3ED36-0HH0 is a 3-pole SENTRON molded case circuit breaker (MCCB) rated for a continuous current Iu of 20 A, with a TM210 thermal-magnetic overcurrent release. It is configured for line protection — meaning its primary role is cable and busbar protection in a distribution panel, not motor or generator protection. The interrupting ratings are 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 7.5 kA at 690 V, which gives you the SCCR headroom for high-fault utility feeds or transformer secondaries. The thermal derating curve is flat from 40 °C to 50 °C at 20 A, then drops to 19.2 A at 55 °C, 18.8 A at 60 °C, 18.4 A at 65 °C, and 18 A at 70 °C. For a panel that runs warm near the top of a switchboard, you can still count on 18 A at 70 °C — no need to oversize a frame for ambient. The rated insulation voltage Ui is 800 V, so it is suitable for 690 V line-line systems common in mining or heavy industrial sites.

Auxiliary and Trip Configuration

This variant ships with 2 auxiliary switches plus 1 trip alarm switch (HQ type), and a shunt trip (STL) auxiliary release. The shunt trip allows remote tripping from a PLC or emergency-stop circuit — useful when the MCCB is in a remote panel and you need a hard-wired trip without a communication module. The integrated auxiliary trip order code is 3VA9688-0BL30, which is the factory-fitted accessory. There is no undervoltage release, no ground fault monitoring, no phase failure detection, and no communication function — this is a pure line-protection breaker with a remote trip capability.

Mechanical Endurance and Environmental Range

The latching endurance is rated at 15,000 operations — typical for a distribution MCCB that sees infrequent switching. The operating temperature range is -25 °C to 70 °C, with storage from -40 °C to 80 °C. Front protection is IP40, which means it is protected against tools and small wires entering from the front, but not against dust ingress from the sides — standard for panel-mounted breakers. Dimensions are 130 mm height, 76.2 mm width, and 70 mm depth, fitting the standard 3-pole SENTRON 3VA footprint.

Frequently asked questions

Where can I buy 3VA1020-3ED36-0HH0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

When sourcing 3VA1020-3ED36-0HH0, what's the closest functional second-source — 3VA1020-3ED36-0AA0?

The 3VA1020-3ED36-0AA0 is the closest peer within the same SENTRON 3VA family. Both are 3-pole, 20 A, TM210 line-protection MCCBs with the same interrupting ratings and dimensions. The -0HH0 variant adds the shunt trip (STL) and the 2 aux + 1 trip alarm switch configuration; the -0AA0 is the base variant without those accessories. If your panel was specified around the -0AA0 and you need the shunt trip, the -0HH0 will drop into the same footprint and bus connections without rewiring — just verify the auxiliary wiring plan.

Will 3VA1020-3ED36-0HH0 drop into a panel that was specified around 3VA1020-3ED36-0AA0 without rewiring?

Yes. Both variants share the same 130 mm height, 76.2 mm width, and 70 mm depth, and the same 3-pole bus-bar connection pattern. The -0HH0 adds the shunt trip and auxiliary switches, so you gain remote trip capability without changing the mounting or power connections.

What compliance documentation does this brand provide for 3VA1020-3ED36-0HH0?

Siemens SENTRON MCCBs carry CE marking for the European market and are designed to meet IEC 60947-2. UL and CSA listings are available for the 3VA platform; the specific listing for this order code should be confirmed from the manufacturer's declaration or the product certificate available via the Siemens Industry Online Support portal.

MPN
3VA1020-3ED36-0HH0