Skip to main content
Siemens 3VA1020-4ED32-0KC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1020-4ED32-0KC0 SENTRON MCCB, 20A, 121kA at 240V

MPN3VA1020-4ED32-0KC0

Siemens SENTRON 3VA1020-4ED32-0KC0, molded case circuit breaker, 3-pole, 20 A rated, 121 kA breaking capacity at 240 V, line protection with shunt trip release.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1020-4ED32-0KC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA10204ED320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA1020-4ED32-0KC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C20 A
Current at 45 °C20 A
Current at 50 °C20 A
Current at 55 °C20 A
Current at 60 °C19 A
Current at 65 °C19 A
Current at 70 °C19 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.12 W

Protection & Trip Unit

3VA1020-4ED32-0KC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1020-4ED32-0KC0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1020-4ED32-0KC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts2

Environmental

3VA1020-4ED32-0KC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1020-4ED32-0KC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

What this MCCB is and what it does

The Siemens SENTRON 3VA1020-4ED32-0KC0 is a 3-pole molded case circuit breaker (MCCB) designed for line protection — meaning it sits at the feeder or branch circuit to guard against overloads and short circuits, not motor or generator protection. It carries a rated current of 20 A across the 40 °C to 55 °C band, derating to 19 A at 60 °C through 70 °C. The breaking capacity is the headline: 121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at both 500 V and 690 V. That 121 kA figure at 240 V tells you this breaker can interrupt a fault current up to that level without failing — critical for high-fault panels near large transformers or upstream of multiple drives.

What the ratings mean for your panel

Rated insulation voltage is 800 V, so the breaker is rated for use in 690 V systems with margin. The 3-pole design fits standard 3-phase feeders. Power loss is 12 W maximum — that's the heat it dumps into the enclosure at full rated current; factor it into your thermal budget if you're stacking multiple breakers in a sealed panel. The auxiliary switch configuration is 2 HQ switches, and the auxiliary release is a shunt trip (STL) — that shunt trip lets you remotely trip the breaker via a control signal, which is useful for emergency-stop circuits or interlocking with a fire alarm system. No undervoltage release, no ground-fault monitoring, no communication function on this variant. It's a straightforward line-protection MCCB with a shunt trip for remote trip capability.

Physical fit and panel integration

Dimensions are 130 mm height, 76.2 mm width, 70 mm depth — that's a standard SENTRON 3VA form factor. It mounts on a DIN rail or can be screw-mounted to a backplate. The 70 mm depth is shallow enough for most 200 mm deep enclosures; check your door clearance if you have a rotary handle mechanism. The width of 76.2 mm (3 inches) is a 3-pole footprint; a 4-pole version would be wider. The shunt trip wiring needs a separate control circuit — factor that into your panel layout.

Frequently asked questions

How do I get current pricing and availability for 3VA1020-4ED32-0KC0?

Submit an RFQ through this listing. We source it to order; availability and current pricing are confirmed at quote time — no speculative lead times here.

What is the breaking capacity of this MCCB at different voltages?

121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at both 500 V and 690 V. That 121 kA at 240 V is the highest rating — it's sized for high-fault panels.

What auxiliary options are fitted on this breaker?

It includes 2 HQ auxiliary switches and a shunt trip (STL) release. No undervoltage release, no ground-fault monitoring, no communication module.

Will 3VA1020-4ED32-0KC0 drop into a panel that was specified around 5SQ2370-2YA05 without rewiring?

Not directly — the 5SQ2370 series is a different form factor and terminal arrangement. The 3VA1020 uses the standard SENTRON 3VA footprint (130 x 76.2 x 70 mm). You'd need to verify mounting hole pattern and busbar spacing before assuming a drop-in swap.

MPN