Siemens 3VA1020-4ED36-0CC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1020-4ED36-0CC0 SENTRON MCCB, 20 A, 121 kA at 240

MPN3VA1020-4ED36-0CC0

Siemens SENTRON 3VA1020-4ED36-0CC0, molded case circuit breaker, 3-pole, 20 A, TM210 trip, 121 kA at 240 V, 70 mm depth.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1020-4ED36-0CC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1020-4ED36-0CC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C20 A
Current at 45 °C20 A
Current at 50 °C20 A
Current at 55 °C19.2 A
Current at 60 °C18.8 A
Current at 65 °C18.4 A
Current at 70 °C18 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 690 V11.9 kA
3VA1020-4ED36-0CC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1020-4ED36-0CC0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1020-4ED36-0CC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts2
3VA1020-4ED36-0CC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1020-4ED36-0CC0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

It carries a 20 A continuous rating across ambient temperatures from 40 °C to 50 °C without derating, then steps down to 18 A at 70 °C — a curve that matters when the breaker lives next to hot busbars in a sealed enclosure. Breaking capacity reaches 121 kA at 240 V, 75.6 kA at 415 V, and still holds 11.9 kA at 690 V — figures that cover most low-voltage fault scenarios in mining and mill distribution without needing a current-limiting upstream device. The TM210 thermal-magnetic trip unit handles overload and short-circuit protection; no electronic communication or phase-failure detection here — it's a pure protective device, not a monitoring node.

Frequently asked questions

Does 3VA1020-4ED36-0CC0 include auxiliary contacts or an undervoltage release?

Yes, it comes with two auxiliary switches (HQ type) and an undervoltage release (UVR) as standard.

MPN
3VA1020-4ED36-0CC0