Skip to main content
Siemens 3VA1025-2ED32-0AH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1025-2ED32-0AH0 SENTRON MCCB, 25 A, 52.5 kA at 24

MPN3VA1025-2ED32-0AH0

Siemens SENTRON 3VA1025-2ED32-0AH0, molded case circuit breaker, 3-pole, 25 A rated continuous current, 52.5 kA breaking capacity at 240 V, TM210 thermal-magnetic release, 2 aux + 1 alarm switch.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1025-2ED32-0AH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1025-2ED32-0AH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C25 A
Current at 45 °C25 A
Current at 50 °C25 A
Current at 55 °C24 A
Current at 60 °C23.5 A
Current at 65 °C23 A
Current at 70 °C22.5 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 690 V7.5 kA
3VA1025-2ED32-0AH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1025-2ED32-0AH0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1025-2ED32-0AH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts3
3VA1025-2ED32-0AH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1025-2ED32-0AH0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens 3VA1025-2ED32-0AH0 is a 3-pole SENTRON molded case circuit breaker rated for 25 A continuous current at 40 °C, with a TM210 thermal-magnetic overcurrent release. Its interrupting capacity hits 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V — so the same unit covers 240 V distribution panels and 400 V motor control centers without a frame-size jump.

Thermal derating — where the 25 A holds and where it tapers

At 55 °C it derates to 24 A, at 60 °C to 23.5 A, at 65 °C to 23 A, and at 70 °C to 22.5 A.

Auxiliary contacts and release configuration

The TM210 release is fixed, not adjustable, so coordination studies should treat the trip curve as factory-set.

Frequently asked questions

Where can I buy 3VA1025-2ED32-0AH0 and what is the lead time?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What are the key ratings for 3VA1025-2ED32-0AH0?

Rated continuous current 25 A, breaking capacity 52.5 kA at 240 V / 32 kA at 415 V / 13.6 kA at 440 V / 7.5 kA at 690 V, rated insulation voltage 800 V, 3-pole, TM210 thermal-magnetic release.

What is the depth of 3VA1025-2ED32-0AH0?

The depth is 70 mm. Width is 76.2 mm, height is 130 mm.

Does 3VA1025-2ED32-0AH0 include auxiliary contacts?

Yes, it comes with 2 auxiliary switches plus 1 trip alarm switch (HQ version).

MPN