SENTRON 3VA1025-2ED32-0BA0 — 25 A MCCB with undervoltage release
It carries a rated insulation voltage of 800 V and delivers interrupting capacity of 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V — figures that let you coordinate selectively with downstream breakers across common industrial voltage levels.
Above that, the thermal curve steps down: 24 A at 55 °C, 23.5 A at 60 °C, 23 A at 65 °C, and 22.5 A at 70 °C. The housing measures 130 mm high, 76.2 mm wide, and 70 mm deep — a standard SENTRON 3VA footprint that clips onto DIN rail.