The 3VA1025-2ED32-0DC0: For BOM freeze or PCN tracking, this part is a safe line-item — no imminent replacement or form-fit-function change is signaled.
Protection & Breaking Capacity
Rated Icu=16kA at 415V AC, this is a class B breaking capacity device per IEC 60947-2 — it safely interrupts faults up to 16 kA without upstream cascading. The TM210 thermal-magnetic trip unit provides fixed overload protection at Ir=25A and fixed short-circuit protection at Ii=12.8 x In (320A magnetic pickup). Selectivity coordination studies should use the fixed Ii value, not an adjustable range.
Integrated Accessories
Two HQ auxiliary switches provide independent status signaling for PLC or remote monitoring. Mounts on standard DIN rail or panel-mount via the 3VA1 frame footprint.