Its interrupting capacity hits 52.5 kA at 240 V and 32 kA at 415 V — figures that govern fault-clearing in low-voltage distribution panels where available fault current runs high.
Compared to the lower-rated 3VA1010-2ED32-0JA0 (10 A frame), this 25 A version shares the same 76.2 mm width and 130 mm height but carries a higher continuous rating and correspondingly higher interrupting duty at each voltage point. Both use the TM210 release family and accept the same 3VA9688-0BL30 integrated auxiliary trip. Panel cutout and busbar spacing are identical, so a swap between the two requires no enclosure modification — only verifying that the downstream load and fault current are within the 25 A frame's limits.
The 70 mm depth fits standard 200 mm deep enclosures; the 76.2 mm width (roughly 3 module spaces) leaves room for adjacent breakers or accessories in a multi-pole lineup.