Skip to main content
Siemens 3VA1025-2ED32-0HC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1025-2ED32-0HC0 SENTRON MCCB, 25 A, 52.5 kA at 24

MPN3VA1025-2ED32-0HC0

Siemens SENTRON 3VA1025-2ED32-0HC0, 3-pole molded case circuit breaker, 25 A rated continuous current, 52.5 kA interrupting capacity at 240 V AC, TM210 thermal-magnetic release, IP40 front protection.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1025-2ED32-0HC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1025-2ED32-0HC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C25 A
Current at 45 °C25 A
Current at 50 °C25 A
Current at 55 °C24 A
Current at 60 °C23.5 A
Current at 65 °C23 A
Current at 70 °C22.5 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 690 V7.5 kA
3VA1025-2ED32-0HC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1025-2ED32-0HC0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1025-2ED32-0HC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts2
3VA1025-2ED32-0HC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1025-2ED32-0HC0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

It carries a 52.5 kA interrupting capacity at 240 V AC, dropping to 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V — so it handles serious fault energy across common industrial voltages without cascading upstream.

The 25 A rating holds steady from 40 °C up to 50 °C, then derates gently to 22.5 A at 70 °C. That means you get full ampacity in most ventilated enclosures without over-speccing the frame size. The TM210 overcurrent release combines a thermal bimetal for overload protection and a magnetic coil for short-circuit trip — no electronics to fail, no auxiliary power needed. The interrupting ratings at different line voltages tell you exactly where it coordinates: 52.5 kA at 240 V for secondary distribution, 32 kA at 415 V for common European industrial supplies, and 7.5 kA at 690 V where fault currents are lower but available energy is still a concern.

The 76.2 mm width (three 25.4 mm pole pitches) and 70 mm depth fit standard SENTRON mounting feet and busbar systems.

Frequently asked questions

How do I get pricing and availability for 3VA1025-2ED32-0HC0?

Submit an RFQ through the distributor. Availability and current pricing are confirmed at quote time — this part is sourced to order through independent channels.

What are the key interrupting ratings for 3VA1025-2ED32-0HC0?

52.5 kA at 240 V AC, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V — enough to clear high-fault-energy events without upstream coordination problems.

What is the continuous current rating at elevated temperatures?

Full 25 A from 40 °C through 50 °C, then derates to 24 A at 55 °C, 23.5 A at 60 °C, 23 A at 65 °C, and 22.5 A at 70 °C.

What type of overcurrent release does this breaker use?

A TM210 thermal-magnetic release — bimetal overload curve plus magnetic short-circuit trip, no electronics to fail.

MPN
3VA1025-2ED32-0HC0