Breaking capacity is 52.5 kA at 240 V AC, dropping to 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 500 V and 690 V. Power loss runs 8.5 W maximum at rated load.
This MCCB mounts in a standard distribution panel or switchboard — it's a panel-mount device, not DIN-rail snap-on. The current rating holds flat at 25 A up to 50 °C, then derates slightly to 24 A at 55-60 °C and 23 A at 65-70 °C.