Skip to main content
Siemens 3VA1025-2ED32-0JH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1025-2ED32-0JH0 SENTRON MCCB, 25 A, 3-Pole, TM210

MPN3VA1025-2ED32-0JH0

Siemens SENTRON 3VA1025-2ED32-0JH0, molded case circuit breaker, 3-pole, 25 A, TM210 thermal-magnetic release, line protection, with shunt trip (STL) and 2 aux + 1 alarm switch, 70 mm depth.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1025-2ED32-0JH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1025-2ED32-0JH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C25 A
Current at 45 °C25 A
Current at 50 °C25 A
Current at 55 °C24 A
Current at 60 °C23.5 A
Current at 65 °C23 A
Current at 70 °C22.5 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 690 V7.5 kA
3VA1025-2ED32-0JH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1025-2ED32-0JH0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1025-2ED32-0JH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts3
3VA1025-2ED32-0JH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1025-2ED32-0JH0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

SENTRON 3VA1025-2ED32-0JH0 — integrator's terse spec recap

Breaking capacity is rated per voltage: 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V. That 52.5 kA at 240 V is high for a 25 A frame — it handles heavy fault current on a 240 V secondary without upstream coordination headaches. This is the workhorse choice for standard motor branch circuits and distribution panels where you don't need the selectivity tuning of an electronic ETU. The 3-pole unit is 76.2 mm wide, 130 mm tall, and 70 mm deep — fits a standard MCCB slot in most Siemens panelboards.

Auxiliary and trip configuration — what ships on this variant

The integrated shunt trip part number is 3VA9688-0BL32 — useful for spares ordering. If you need undervoltage release or Modbus, this is not the right variant; look at the 3VA2 family with electronic releases. Mechanical endurance is 15,000 operations (latching type).

No official successor exists because the part is current. If you need a functional cross-reference within the same SENTRON 3VA family, the closest peers are 3VA1010-2ED42-0AE0 (10 A frame, different trip and aux config) and 3VA1020-3ED36-0AA0 (20 A, 3-pole, different release) — but the 3VA1025-2ED32-0JH0 is the 25 A variant with the specific shunt trip and HQ aux switch combination. Panel footprint is the same 3-pole 70 mm depth across the 3VA1/2 series, so a drop-in replacement for a panel originally specced around a 3VA1010-2ED42-0AE0 would only work if the amp rating matches the load — you cannot simply swap a 10 A for a 25 A without checking the branch circuit protection.

Panel integration — what to know before the wire hits the lug

The TM210 release is non-interchangeable — the trip unit is integral to the breaker. If you need field-adjustable thermal or magnetic settings, you are looking at the 3VA2 electronic-trip family. For a fixed 25 A branch circuit with shunt trip and remote status (2 aux + 1 alarm), this variant is the correct pick.

Frequently asked questions

Who supplies 3VA1025-2ED32-0JH0 and how is it quoted for volume purchases?

The 3VA1025-2ED32-0JH0 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for firm pricing and lead time on volume.

What is the closest functional second-source to 3VA1025-2ED32-0JH0?

Within the SENTRON 3VA family, the closest peers are 3VA1010-2ED42-0AE0 (10 A frame) and 3VA1020-3ED36-0AA0 (20 A frame), but neither is a direct replacement — the 3VA1025-2ED32-0JH0 is the 25 A variant with the specific shunt trip and HQ auxiliary switch combination. Panel footprint (3-pole, 70 mm deep) is shared, so mechanical fit is the same, but amp rating must match the branch circuit.

What is the depth of 3VA1025-2ED32-0JH0?

The 3VA1025-2ED32-0JH0 has a depth of 70 mm, width of 76.2 mm, and height of 130 mm.

What compliance documentation does the SENTRON 3VA series carry?

The SENTRON 3VA series carries IEC/EN 60947-2 certification for MCCBs. The specific order code 3VA1025-2ED32-0JH0 is a line protection device with IP40 front protection, reference code Q per DIN EN 81346-2. For specific RoHS/REACH/UL declarations, refer to the Siemens declaration of conformity for the 3VA family — the evidence does not list individual cert numbers.

MPN
3VA1025-2ED32-0JH0