Rated 25 A continuously from 40 °C down to 50 °C; derates to 23 A at 65–70 °C, which matters if the breaker sits next to heat-generating contactors in a sealed enclosure. Interrupting capacity drops with voltage: 52.5 kA at 415 V, 32 kA at 440 V, 7.5 kA at 500 V and 690 V — check your system voltage and available fault current before committing the BOM line. Maximum power loss 8.5 W, typical for this frame size; factor into enclosure thermal calculations. Dimensions are 130 mm height, 76.2 mm width, 70 mm depth — standard SENTRON 3VA1 frame footprint. Trip indicator visible on the front face for quick visual check during commissioning.

Siemens 3VA1025-3ED32-0AF0 SENTRON MCCB, 25A, 3-Pole, 75.6kA
Siemens SENTRON, molded case circuit breaker, 3VA1025-3ED32-0AF0, 3-pole, 25 A (40 °C), 75.6 kA interrupting at 240 V AC, TM210 release, line protection.
Specifications
| Parameter | Value |
|---|---|
| Product designation | Molded case circuit breaker |
| Brand / range | SENTRON |
| Basic switch (supplied) ref. | 3VA10253ED320AA0 |
| Integrated auxiliary / alarm switch ref. | 3VA9988-0AB12 |
| Parameter | Value |
|---|---|
| Number of poles | 3 |
| Rated operational voltage Ue (AC) | 690 V |
| Rated insulation voltage Ui | 800 V |
| Current at 40 °C | 25 A |
| Current at 45 °C | 25 A |
| Current at 50 °C | 25 A |
| Current at 55 °C | 24 A |
| Current at 60 °C | 24 A |
| Current at 65 °C | 23 A |
| Current at 70 °C | 23 A |
| Switching capacity class | N |
| Breaking capacity at 240 V | 75.6 kA |
| Breaking capacity at 415 V | 52.5 kA |
| Breaking capacity at 440 V | 32 kA |
| Breaking capacity at 500 V | 7.5 kA |
| Breaking capacity at 690 V | 7.5 kA |
| Power loss, max. | 8.5 W |
| Parameter | Value |
|---|---|
| Overcurrent release (trip unit) type | TM210 |
| Overcurrent protection function | LI |
| Ground-fault monitoring | Without |
| Grounding protection function | No |
| Parameter | Value |
|---|---|
| Main circuit connection type | nut keeper kit on both ends |
| Main circuit connector arrangement | Front terminal |
| Protection class (IP), front | IP40 |
| Parameter | Value |
|---|---|
| Undervoltage release | No |
| Voltage trigger | No |
| Trip indicator | Yes |
| Communication function | No |
| Measurement function | No |
| Motor drive option | No |
| Auxiliary CO contacts | 2 |
| Parameter | Value |
|---|---|
| Operating temperature, max. | 70 °C |
| Operating temperature, min. | -25 °C |
| Storage temperature, max. | 80 °C |
| Storage temperature, min. | -40 °C |
| Parameter | Value |
|---|---|
| Mechanical service life (operating cycles), typ. | 20 000 |
| Height | 130 mm |
| Width | 76.2 mm |
| Depth | 70 mm |
| Height (in) | 5.12 in |
| Width (in) | 3 in |
| Depth (in) | 2.76 in |
Product details
Frequently asked questions
Where can I buy 3VA1025-3ED32-0AF0 and get a price?
This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.
What is the interrupting capacity of 3VA1025-3ED32-0AF0 at 240 V?
75.6 kA at 240 V AC. At 415 V it is 52.5 kA, at 440 V it is 32 kA, and at 500/690 V it is 7.5 kA.
What compliance documentation is available for this SENTRON MCCB?
Standard Siemens SENTRON documentation includes RoHS and REACH declarations; UL and IEC certifications are typical for the series. Specific certificate copies are available on request with the RFQ.