Skip to main content
Siemens 3VA1025-3ED32-0AF0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1025-3ED32-0AF0 SENTRON MCCB, 25A, 3-Pole, 75.6kA

MPN3VA1025-3ED32-0AF0

Siemens SENTRON, molded case circuit breaker, 3VA1025-3ED32-0AF0, 3-pole, 25 A (40 °C), 75.6 kA interrupting at 240 V AC, TM210 release, line protection.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1025-3ED32-0AF0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA10253ED320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1025-3ED32-0AF0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C25 A
Current at 45 °C25 A
Current at 50 °C25 A
Current at 55 °C24 A
Current at 60 °C24 A
Current at 65 °C23 A
Current at 70 °C23 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V7.5 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.8.5 W
3VA1025-3ED32-0AF0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1025-3ED32-0AF0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1025-3ED32-0AF0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts2
3VA1025-3ED32-0AF0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1025-3ED32-0AF0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

Rated 25 A continuously from 40 °C down to 50 °C; derates to 23 A at 65–70 °C, which matters if the breaker sits next to heat-generating contactors in a sealed enclosure. Interrupting capacity drops with voltage: 52.5 kA at 415 V, 32 kA at 440 V, 7.5 kA at 500 V and 690 V — check your system voltage and available fault current before committing the BOM line. Maximum power loss 8.5 W, typical for this frame size; factor into enclosure thermal calculations. Dimensions are 130 mm height, 76.2 mm width, 70 mm depth — standard SENTRON 3VA1 frame footprint. Trip indicator visible on the front face for quick visual check during commissioning.

Frequently asked questions

Where can I buy 3VA1025-3ED32-0AF0 and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the interrupting capacity of 3VA1025-3ED32-0AF0 at 240 V?

75.6 kA at 240 V AC. At 415 V it is 52.5 kA, at 440 V it is 32 kA, and at 500/690 V it is 7.5 kA.

What compliance documentation is available for this SENTRON MCCB?

Standard Siemens SENTRON documentation includes RoHS and REACH declarations; UL and IEC certifications are typical for the series. Specific certificate copies are available on request with the RFQ.

MPN
3VA1025-3ED32-0AF0