Skip to main content
Siemens 3VA1025-3ED32-0AH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1025-3ED32-0AH0 SENTRON MCCB, 25 A, 3-Pole, 70 mm

MPN3VA1025-3ED32-0AH0

Siemens SENTRON 3VA1025-3ED32-0AH0, molded case circuit breaker, 3-pole, 25 A rated continuous current Iu, TM210 overcurrent release, 70 mm depth, IP40 front protection.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1025-3ED32-0AH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1025-3ED32-0AH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C25 A
Current at 45 °C25 A
Current at 50 °C25 A
Current at 55 °C24 A
Current at 60 °C23.5 A
Current at 65 °C23 A
Current at 70 °C22.5 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 690 V7.5 kA
3VA1025-3ED32-0AH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1025-3ED32-0AH0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1025-3ED32-0AH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts3
3VA1025-3ED32-0AH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1025-3ED32-0AH0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

SENTRON 3VA1025-3ED32-0AH0 — 25 A MCCB with TM210 Release

Its breaking capacity varies by system voltage: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 7.5 kA at 690 V — covering most low-voltage distribution and motor branch circuits in industrial panels.

Thermal Derating and Continuous Current

The 25 A rating holds flat from 40 °C through 50 °C, then derates to 24 A at 55 °C, 23.5 A at 60 °C, 23 A at 65 °C, and 22.5 A at 70 °C — a 10 % drop at the upper operating limit. This means a panel designer can count on full 25 A capability in typical 40–50 °C enclosures; above that, the load must be trimmed or the breaker upsized to the next frame.

Auxiliary Contacts and Trip Indication

The trip indicator provides local visual confirmation of a thermal or magnetic trip event, useful during commissioning and fault isolation.

MPN