Skip to main content
Siemens 3VA1025-3ED32-0BA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1025-3ED32-0BA0 SENTRON MCCB, 25 A, 3-Pole, 70 mm

MPN3VA1025-3ED32-0BA0

Siemens SENTRON 3VA1025-3ED32-0BA0, molded case circuit breaker, 3-pole, 25 A (40 °C), line protection, undervoltage release, 70 mm depth, 76.2 mm width, 130 mm height.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1025-3ED32-0BA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA10253ED320AA0
3VA1025-3ED32-0BA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C25 A
Current at 45 °C25 A
Current at 50 °C25 A
Current at 55 °C24 A
Current at 60 °C24 A
Current at 65 °C23 A
Current at 70 °C23 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V7.5 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.11 W
3VA1025-3ED32-0BA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1025-3ED32-0BA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1025-3ED32-0BA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA1025-3ED32-0BA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1025-3ED32-0BA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

Siemens SENTRON 3VA1025-3ED32-0BA0 — 25 A MCCB with Undervoltage Release

Breaking capacity is voltage-dependent: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 7.5 kA at both 500 V and 690 V. Dimensions are 70 mm deep, 76.2 mm wide, and 130 mm high — a standard footprint for SENTRON 3VA frame sizes, allowing direct panel integration without re-drilling in most retrofit scenarios.

At 55 °C it derates to 24 A, holds 24 A at 60 °C, then steps to 23 A at both 65 °C and 70 °C. This derating curve is typical for thermal-magnetic MCCBs and must be factored into panel design when the breaker is enclosed or adjacent to other heat sources.

The 3-pole design occupies 76.2 mm (3 in) of rail width. Spring-cage or screw terminals accept copper conductors sized per the 25 A rating; torque settings follow the manufacturer's installation instructions. The undervoltage release coil must be wired to a separate control voltage source — verify polarity and coil rating against the control circuit.

Frequently asked questions

Where can I buy 3VA1025-3ED32-0BA0 and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing — no stock count or price figure is published here.

What is the breaking capacity of 3VA1025-3ED32-0BA0 at 415 V?

52.5 kA at 415 V. Breaking capacity varies by voltage: 75.6 kA at 240 V, 32 kA at 440 V, and 7.5 kA at both 500 V and 690 V.

Does 3VA1025-3ED32-0BA0 include an undervoltage release?

Yes, it is equipped with an undervoltage release (UVR) of the TM210 type, designed to trip the breaker when control voltage drops below a threshold.

MPN