Skip to main content
Siemens 3VA1025-3ED32-0BH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1025-3ED32-0BH0 SENTRON MCCB, 25 A, 3-Pole

MPN3VA1025-3ED32-0BH0

Siemens SENTRON 3VA1025-3ED32-0BH0, 3-pole molded case circuit breaker, 25 A rated current at 40 °C, breaking capacity 75.6 kA at 240 V, with undervoltage release.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1025-3ED32-0BH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA10253ED320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1025-3ED32-0BH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C25 A
Current at 45 °C25 A
Current at 50 °C25 A
Current at 55 °C24 A
Current at 60 °C24 A
Current at 65 °C23 A
Current at 70 °C23 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V7.5 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.11 W
3VA1025-3ED32-0BH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1025-3ED32-0BH0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1025-3ED32-0BH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts3
3VA1025-3ED32-0BH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1025-3ED32-0BH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

The 3VA1025-3ED32-0BH0: Includes an undervoltage release (UVR) that drops the breaker when control power falls below threshold.

That's a shallow derating curve; the breaker doesn't lose much headroom as the enclosure heats up. That's the heat each unit dumps into the cabinet at full load, and it adds up fast in a multi-circuit panel.

What the breaking capacity numbers tell you

Breaking capacity drops as system voltage climbs: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 7.5 kA at both 500 V and 690 V. At typical 400/415 V distribution, 52.5 kA handles most secondary-side faults.

Frequently asked questions

What are the physical dimensions of this MCCB?

Height is 130 mm, width 76.2 mm, and depth 70 mm — a standard MCCB envelope that fits most panel-mount and DIN-rail enclosures.

MPN