Skip to main content
Siemens 3VA1025-3ED32-0JH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1025-3ED32-0JH0 SENTRON MCCB, 25 A, 3-Pole, 75.6

MPN3VA1025-3ED32-0JH0

Siemens SENTRON 3VA1025-3ED32-0JH0, 3-pole molded case circuit breaker, 25 A rated at 40 °C, breaking capacity 75.6 kA at 240 V AC, line protection design, with shunt trip and auxiliary switches.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1025-3ED32-0JH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA10253ED320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA1025-3ED32-0JH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C25 A
Current at 45 °C25 A
Current at 50 °C25 A
Current at 55 °C24 A
Current at 60 °C24 A
Current at 65 °C23 A
Current at 70 °C23 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V7.5 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.8.5 W

Protection & Trip Unit

3VA1025-3ED32-0JH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1025-3ED32-0JH0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1025-3ED32-0JH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts3

Environmental

3VA1025-3ED32-0JH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1025-3ED32-0JH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

What it is and what it does

The Siemens 3VA1025-3ED32-0JH0 is a SENTRON molded case circuit breaker (MCCB) designed for line protection in industrial and commercial power distribution. It is a 3-pole unit rated 25 A at 40 °C, with a maximum breaking capacity of 75.6 kA at 240 V AC. The insulation voltage is rated 800 V, so it handles 480Y/277 V and 600 V panel feeds without issue.

Breaking capacity across voltages

This MCCB delivers 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 7.5 kA at 500 V and 690 V. That means it can clear high-fault currents on the secondary side of a 150 kVA transformer, but at 480 V the available fault current needs to stay under 32 kA — typical for most industrial panelboards. The 7.5 kA at 690 V covers 690 V drives or mining gear.

Thermal derating and operating range

Rated 25 A continuous from 40 °C up to 50 °C. At 55 °C it derates to 24 A, and at 70 °C it holds 23 A. That's a shallow derating curve — useful if the breaker sits in a warm enclosure near other heat sources. Ambient operating range is -25 °C to 70 °C; storage from -40 °C to 80 °C. Maximum power loss is 8.5 W.

Auxiliary and release configuration

Factory-fitted with 2 auxiliary switches plus 1 trip alarm switch (HQ configuration), and a shunt trip release (STL). No undervoltage release, no ground-fault monitoring, no communication module. The shunt trip allows remote tripping from a PLC or E-stop circuit — common for safety isolation in conveyor or HVAC systems.

Panel fit and dimensions

The 3VA1025-3ED32-0JH0 measures 130 mm high, 76.2 mm wide, and 70 mm deep. It mounts on a DIN rail or can be screw-fixed in a panel. The 76.2 mm width (3 inches) is a standard 3-pole MCCB footprint — fits existing busbar and enclosure cutouts without modification. The depth of 70 mm (2.76 in) leaves room for rear-access wiring in a 200 mm deep enclosure.

Frequently asked questions

How do I get pricing and availability for 3VA1025-3ED32-0JH0?

Submit an RFQ through this listing; pricing and lead time are confirmed at quote time through independent distribution.

What is the breaking capacity of this MCCB at 240 V?

75.6 kA at 240 V AC, with 52.5 kA at 415 V and 32 kA at 440 V.

Does the 3VA1025-3ED32-0JH0 include a shunt trip?

Yes, it comes with a shunt trip release (STL) plus 2 auxiliary switches and 1 trip alarm switch.

MPN
3VA1025-3ED32-0JH0