Skip to main content
Siemens 3VA1025-3ED46-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1025-3ED46-0AA0 SENTRON MCCB, 25A, 4-Pole, 75.6kA

MPN3VA1025-3ED46-0AA0
Active

Siemens SENTRON 3VA1025-3ED46-0AA0, molded case circuit breaker, 4-pole, 25 A (40 °C), TM210 overcurrent release, line protection, 75.6 kA at 240 V, IP40 front.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1025-3ED46-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA1025-3ED46-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C25 A
Current at 45 °C25 A
Current at 50 °C25 A
Current at 55 °C24 A
Current at 60 °C24 A
Current at 65 °C23 A
Current at 70 °C23 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V7.5 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.8.5 W
3VA1025-3ED46-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1025-3ED46-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1025-3ED46-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA1025-3ED46-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1025-3ED46-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.12 in
Width (in)4 in
Depth (in)2.76 in

Product details

The 3VA1025-3ED46-0AA0 is a SENTRON molded case circuit breaker (MCCB) rated 25 A at 40 °C, with a TM210 thermal-magnetic overcurrent release and 4-pole configuration for three-phase-plus-neutral line protection. Breaking capacity hits 75.6 kA at 240 V, 52.5 kA at 415 V, and 32 kA at 440 V — enough to handle high-fault industrial distribution panels without cascading upstream.

Full 25 A holds from 40 °C through 50 °C; at 55 °C it derates to 24 A, and at 70 °C it drops to 23 A. That means a 40 °C panel ambient keeps the full rating, but a hot control room near a kiln or furnace costs you 1–2 A. Maximum power loss is 8.5 W — negligible for panel heat budget, but worth noting if you pack twenty of these in a sealed cabinet.

Footprint is 101.6 mm wide, 130 mm tall, 70 mm deep — a standard 4-pole MCCB envelope that fits most DIN-rail or panel-mount backplates without re-drilling. The TM210 release is fixed, no communication module, no undervoltage release — a straightforward thermal-magnetic breaker for basic feeder protection.

Frequently asked questions

What trip unit does the 3VA1025-3ED46-0AA0 use?

It uses a TM210 thermal-magnetic overcurrent release — fixed, non-interchangeable, designed for line protection with no communication function or undervoltage release.