Skip to main content
Siemens 3VA1025-4ED32-0AC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1025-4ED32-0AC0 SENTRON MCCB, 25 A, 121 kA at 240

MPN3VA1025-4ED32-0AC0

Siemens SENTRON 3VA1025-4ED32-0AC0, molded case circuit breaker, 3-pole, 25 A rated continuous current Iu, TM210 thermal-magnetic release, 121 kA breaking capacity at 240 V AC, 2 auxiliary switches HQ, IP40 front protection.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1025-4ED32-0AC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA1025-4ED32-0AC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C25 A
Current at 45 °C25 A
Current at 50 °C25 A
Current at 55 °C24 A
Current at 60 °C23.5 A
Current at 65 °C23 A
Current at 70 °C22.5 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 690 V11.9 kA

Protection & Trip Unit

3VA1025-4ED32-0AC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210

Construction & Connection

3VA1025-4ED32-0AC0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1025-4ED32-0AC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts2

Environmental

3VA1025-4ED32-0AC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1025-4ED32-0AC0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

What this MCCB carries and where it fits

The Siemens SENTRON 3VA1025-4ED32-0AC0 is a 3-pole molded case circuit breaker rated for 25 A continuous current (Iu) with a TM210 thermal-magnetic overcurrent release. Its breaking capacity hits 121 kA at 240 V AC, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at 690 V — numbers that tell you this unit handles high-fault-current industrial distribution panels, not just branch circuits. The TM210 release means the thermal element is fixed at 25 A (no field adjustment), while the magnetic trip is set at 10× In, so it clears bolted faults fast without nuisance tripping on motor inrush. Two HQ auxiliary switches are built in for status feedback to a PLC or annunciator panel. The 70 mm depth and 76.2 mm width (standard 3-pole MCCB footprint) let it drop into existing SENTRON or third-party panelboards without re-drilling the mounting plate. Front IP40 protection keeps out tool drops and dust during installation; the enclosure is rated for operation from -25 °C to 70 °C and storage from -40 °C to 80 °C, covering most indoor industrial environments.

Current derating across temperature

This breaker holds its full 25 A rating from 40 °C through 50 °C ambient. At 55 °C it derates to 24 A, at 60 °C to 23.5 A, at 65 °C to 23 A, and at 70 °C to 22.5 A. If the panel sits near a heat source or in a non-ventilated enclosure, check the actual ambient at the breaker — a 25 A continuous load at 65 °C would need the next frame up.

Frequently asked questions

What is the breaking capacity of 3VA1025-4ED32-0AC0 at 415 V?

75.6 kA at 415 V AC. At 240 V it is 121 kA, at 440 V it is 52.5 kA, and at 690 V it is 11.9 kA.

Where can I buy 3VA1025-4ED32-0AC0 and how is it quoted?

This part is sourced to order through independent distribution. Submit an RFQ for current availability and pricing — stock and lead time are confirmed at quote time.

Will 3VA1025-4ED32-0AC0 fit in a panel designed for 3VA1010-4ED32-0AC0?

Yes, the 70 mm depth and 76.2 mm width are identical across the 3VA frame sizes. The 25 A unit drops into the same mounting footprint without rewiring the bus bars.

What auxiliary contacts does this MCCB include?

Two HQ auxiliary switches are factory-installed. No undervoltage release or shunt trip is fitted on this variant.

MPN
3VA1025-4ED32-0AC0