Its breaking capacity hits 121 kA at 240 V AC, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at 690 V — numbers that tell you this unit handles high-fault-current industrial distribution panels, not just branch circuits. Front IP40 protection keeps out tool drops and dust during installation; the enclosure is rated for operation from -25 °C to 70 °C and storage from -40 °C to 80 °C, covering most indoor industrial environments.
Current derating across temperature