Skip to main content
Siemens 3VA1025-4ED32-0CC0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA1025-4ED32-0CC0 MCCB, 25A, 3-Pole, 121kA

MPN3VA1025-4ED32-0CC0

Siemens SENTRON 3VA1025-4ED32-0CC0, molded case circuit breaker (MCCB), 3-pole, 25 A rated at 40 °C, breaking capacity 121 kA at 240 V AC, line protection design, with undervoltage release and 2 auxiliary switches HQ.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1025-4ED32-0CC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA10254ED320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1025-4ED32-0CC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C25 A
Current at 45 °C25 A
Current at 50 °C25 A
Current at 55 °C24 A
Current at 60 °C24 A
Current at 65 °C23 A
Current at 70 °C23 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.11 W
3VA1025-4ED32-0CC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1025-4ED32-0CC0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1025-4ED32-0CC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts2
3VA1025-4ED32-0CC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1025-4ED32-0CC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

The Siemens SENTRON 3VA1025-4ED32-0CC0 is a 3-pole molded case circuit breaker (MCCB) rated 25 A at 40 °C, with a breaking capacity of 121 kA at 240 V AC. At 415 V the interrupting rating drops to 75.6 kA, and at 690 V to 11.9 kA, so verify the available fault current at your service voltage before specifying. The breaker carries a continuous current rating that holds at 25 A from 40 °C through 50 °C, then derates to 24 A at 55–60 °C and 23 A at 65–70 °C — a gentle slope that gives headroom in warm enclosures.

Maximum power loss is 11 W, which is moderate for a 25 A MCCB. In a densely packed panel, that heat adds to the enclosure rise — account for it in the thermal budget if the breaker is mounted alongside other heat sources.

Footprint is 76.2 mm wide by 130 mm tall by 70 mm deep — a standard 3-pole MCCB width that fits most DIN-rail or panel-mount enclosures without surprises.

Frequently asked questions

Does this MCCB include an undervoltage release?

Yes, it ships with an undervoltage release (UVR) and two HQ auxiliary switches factory-installed.

MPN
3VA1025-4ED32-0CC0