Skip to main content
Siemens 3VA1032-2ED32-0AC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1032-2ED32-0AC0 SENTRON MCCB, 32 A, 52.5 kA at 24

MPN3VA1032-2ED32-0AC0

Siemens SENTRON 3VA1032-2ED32-0AC0, 3-pole molded case circuit breaker, 32 A rated continuous current, 52.5 kA breaking capacity at 240 V, TM210 thermal-magnetic release, 2 auxiliary switches HQ.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA1032-2ED32-0AC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1032-2ED32-0AC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C32 A
Current at 45 °C32 A
Current at 50 °C32 A
Current at 55 °C30.72 A
Current at 60 °C30.08 A
Current at 65 °C29.44 A
Current at 70 °C28.8 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 690 V7.5 kA
3VA1032-2ED32-0AC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1032-2ED32-0AC0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1032-2ED32-0AC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts2
3VA1032-2ED32-0AC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1032-2ED32-0AC0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens 3VA1032-2ED32-0AC0 is a 3-pole SENTRON molded case circuit breaker rated for 32 A continuous current at 40 °C, with a TM210 thermal-magnetic release that provides fixed thermal and magnetic trip settings for line protection. Its interrupting capacity reaches 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V — enough to handle high-fault scenarios in industrial distribution panels without cascading upstream.

At 76.2 mm wide, 130 mm tall, and 70 mm deep, this MCCB fits standard SENTRON 3VA panel cutouts and busbar systems. No undervoltage release or phase-failure detection is built in — those functions would need an external add-on module.

Frequently asked questions

What is the breaking capacity of this MCCB at 415 V?

32 kA at 415 V, which covers most industrial low-voltage distribution fault levels.

Where can I buy 3VA1032-2ED32-0AC0 and how is it quoted?

Sourced to order through independent distribution; submit an RFQ for current pricing and availability.

MPN
3VA1032-2ED32-0AC0