Skip to main content
Siemens 3VA1032-2ED32-0AE0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA1032-2ED32-0AE0 MCCB, 32 A, 52.5 kA

MPN3VA1032-2ED32-0AE0

Siemens SENTRON 3VA1032-2ED32-0AE0, 3-pole molded case circuit breaker, 32 A rated continuous current, TM210 thermal-magnetic release, 52.5 kA breaking capacity at 240 V, 4 auxiliary switches HQ, IP40 front protection.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA1032-2ED32-0AE0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1032-2ED32-0AE0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C32 A
Current at 45 °C32 A
Current at 50 °C32 A
Current at 55 °C30.72 A
Current at 60 °C30.08 A
Current at 65 °C29.44 A
Current at 70 °C28.8 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 690 V7.5 kA
3VA1032-2ED32-0AE0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1032-2ED32-0AE0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1032-2ED32-0AE0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts4
3VA1032-2ED32-0AE0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1032-2ED32-0AE0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

32 A MCCB with 52.5 kA interrupting capacity — SENTRON 3VA series

Its interrupting capacity hits 52.5 kA at 240 V AC, 32 kA at 415 V, and 7.5 kA at 690 V — so it handles high-fault scenarios on the secondary side of a distribution transformer or at a motor control center feeder without cascading upstream. The TM210 release is fixed (non-adjustable thermal and magnetic trip), which simplifies coordination studies: you know the exact trip curve without field calibration. The breaker carries 32 A straight through 50 °C ambient; above that it derates gradually to 28.8 A at 70 °C — useful if the breaker lives in a non-ventilated enclosure near other heat sources.

Deployment context — panel integration and auxiliary wiring

IP40 on the front. The four auxiliary switches HQ provide two NO + two NC contacts.

At 415 V (common in European industrial systems) it still handles 32 kA, which covers most transformer-fed panels. The 690 V rating of 7.5 kA is lower but still adequate for many motor-feeder applications on 690 V networks.

MPN