Skip to main content
Siemens 3VA1032-2ED32-0CA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1032-2ED32-0CA0 SENTRON MCCB, 32 A, 3-Pole, 52.5

MPN3VA1032-2ED32-0CA0

Siemens SENTRON 3VA1032-2ED32-0CA0, molded case circuit breaker, 32 A, 3-pole, 52.5 kA interrupting at 240 V, TM210 overcurrent release, undervoltage release.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1032-2ED32-0CA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA10322ED320AA0
3VA1032-2ED32-0CA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C32 A
Current at 45 °C32 A
Current at 50 °C32 A
Current at 55 °C31 A
Current at 60 °C31 A
Current at 65 °C30 A
Current at 70 °C30 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 500 V7.5 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.13.1 W
3VA1032-2ED32-0CA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1032-2ED32-0CA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1032-2ED32-0CA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA1032-2ED32-0CA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1032-2ED32-0CA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

The Siemens SENTRON 3VA1032-2ED32-0CA0 is a 3-pole molded case circuit breaker rated 32 A continuous at 40 °C, with a TM210 thermal-magnetic overcurrent release and an integrated undervoltage release (UVR). Interrupting capacity hits 52.5 kA at 240 V AC and 32 kA at 415 V AC — enough for high-fault panel feeders or distribution mains. The UVR drops the breaker on loss of control voltage, standard for safety disconnects or emergency-off chains.

Interrupting capacity and coordination

At 240 V the 52.5 kA rating handles utility-side faults without cascading upstream. At 415 V it still holds 32 kA, and at 690 V it's 7.5 kA — so on 690 V industrial circuits this breaker is for moderate-fault nodes, not the main. The TM210 release is fixed thermal-magnetic; no electronic trip unit, so coordination studies need the published time-current curve.

Width is 76.2 mm (3 in), depth 70 mm (2.76 in), height 130 mm (5.12 in) — standard SENTRON 3VA frame footprint. The undervoltage release (UVR) is factory-fitted; verify coil voltage matches the control circuit before wiring. Line protection design means no communication module or ground-fault option on this order code.

Frequently asked questions

What is the interrupting capacity of 3VA1032-2ED32-0CA0 at different voltages?

52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at both 500 V and 690 V.

Does 3VA1032-2ED32-0CA0 include an undervoltage release?

Yes, it is fitted with an undervoltage release (UVR) as standard.

Where can I buy 3VA1032-2ED32-0CA0 and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no online stock or price is posted.

MPN
3VA1032-2ED32-0CA0