Skip to main content
Siemens 3VA1032-2ED32-0CH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1032-2ED32-0CH0 SENTRON MCCB, 32 A, 3-Pole, Line

MPN3VA1032-2ED32-0CH0

Siemens SENTRON 3VA1032-2ED32-0CH0, molded case circuit breaker, 3-pole, 32 A rated continuous current Iu, line protection version with TM210 thermal-magnetic release, 52.5 kA breaking at 240 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA1032-2ED32-0CH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1032-2ED32-0CH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C32 A
Current at 45 °C32 A
Current at 50 °C32 A
Current at 55 °C30.72 A
Current at 60 °C30.08 A
Current at 65 °C29.44 A
Current at 70 °C28.8 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 690 V7.5 kA
3VA1032-2ED32-0CH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1032-2ED32-0CH0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1032-2ED32-0CH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts3
3VA1032-2ED32-0CH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1032-2ED32-0CH0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

32 A MCCB with TM210 release — line protection for distribution panels

Its TM210 thermal-magnetic release handles overload and short-circuit curves without external trip units — a fixed-trip design that simplifies BOM management on panel builds where the customer's approved vendor list (AVL) specifies SENTRON for the distribution section. Rated 32 A at 40 °C through 50 °C without derating; above 50 °C the current tapers to 28.8 A at 70 °C. That thermal profile means the breaker holds its full rating across most panel ambient conditions — only above 55 °C does the integrator need to check the derate curve against the actual enclosure temperature. Breaking capacity is 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V. For a 415 V distribution board this gives 32 kA SCCR — enough to coordinate with most downstream panelboard breakers without requiring a current-limiting upstream device.

Integrated undervoltage release and auxiliary contacts

That is a common requirement for safety circuits and emergency-stop chains where the MCCB must open when the control supply drops. The alarm switch changes state only on a fault trip, not on manual switching — useful for remote annunciation in a PLC input or a panel lamp circuit. The 3-pole footprint measures 76.2 mm wide by 130 mm tall by 70 mm deep, matching the standard SENTRON 3VA mounting grid for busbar or cable connection.

Current lifecycle — active production, no phase-out notice

The integrated auxiliary trip accessory is order code 3VA9608-0BB24 — if the panel BOM already carries that accessory, verify it matches this breaker's release interface.

Frequently asked questions

Does 3VA1032-2ED32-0CH0 include an undervoltage release?

Yes — this order code ships with an undervoltage release (UVR) fitted as the auxiliary release. It also includes 2 auxiliary switches plus 1 trip alarm switch (HQ configuration).

MPN
3VA1032-2ED32-0CH0